Communications
vacon • 35
24-hour s358 (0)201 212 575 • Email: [email protected]
6
Table 23.
Status Word bits
The Status word is composed of 32 bits. The meanings of bits are described below.
Table 25. Status Word bits B1-B28
Table 24.
Bit
Name
Value=1
Value=2
Vacon 100
HVAC
Vacon 100
Bit 0
Ready
Ready for opera-
tion
Not Ready
Supported
Supported
Bit 01
Run
Running
Stopped
Supported
Supported
Bit 2
Direction
Counterclockwise
Clockwise
Supported
Supported
Bit 3
Fault
A fault is active
No fault active
Supported
Supported
Bit 4
Alarm
An alarm is active No alarm active
Supported
Supported
Bit 5
At Reference
Reference fre-
quency is reached
Reference fre-
quency is not
reached
Supported
Supported
Bit 6
Zero Speed
Motor is at zero
speed
Motor is at non-
zero speed
Supported
Supported
Bit 7
Flux Ready
Motor is magne-
tized
Motor is not
magnetized
Supported
Supported
Bit 8-28
Reserved
Not used
Supported
Supported
Table 26:
Bit
Name
Value = 1
Value = 0
Description
B0
Ready
Ready
Not ready
Indicates whether the drive is
ready or not
B1
Run
Running
Stop
Indicates whether the drive is
running or stopped
B2
Direction
Counterclockwise
Clockwise
Indicates the rotation direc-
tion of the motor
B3
Fault
Faulted
Not faulted
Indicates if a fault is active
B4
Alarm
Alarm
No alarm
Indicates if an alarm is active
B5
AtReference
True
False
Reference frequency reached
B6
ZeroSpeed
True
False
Motor running at zero speed
B7
FluxReady
True
False
Motor is magnetized
B8-B28 Not used