Annex
vacon • 49
24-hour s358 (0)201 212 575 • Email: [email protected]
9
9.
A
NNEX
Process Data IN (Master to Slave)
Use of Process Data In variables depends on the used application. The configuration of the data is
free.
Process Data OUT (Slave to Master)
Use of Process Data Out variables depends on the used application.
The Fieldbus Master can read the AC drive’s actual values using process data variables. Control
applications use process data as follows:
Table 50. Process Data OUT variables
NOTE 1!
In Vacon 100, the Motor Current scale depends on the drive size. In Vacon 100 HVAC the
Motor Current scale is always 0.1 A.
NOTE 2!
In Vacon 100 HVAC, the default ID is 45 meaning "Motor Current 1 Decimal". In Vacon 100,
the default ID is 3 for Motor Current. The ID 45 can be mapped by the user to this variable also in
Vacon 100.
Table 51.
Register
Data
Default ID
Information
Unit
2104
Process data OUT 1
1
Output Frequency
0.01 Hz
2105
Process data OUT 2
2
Motor Speed
1 rpm
2106
Process data OUT 3
3(45)
2
Motor Current
0.1 A
2107
Process data OUT 4
4
Motor Torque
0.1 %
2108
Process data OUT 5
5
Motor Power
0.1 %
2109
Process data OUT 6
6
Motor Voltage
0.1 V
2110
Process data OUT 7
7
DC link voltage
1 V
2111
Process data OUT 8
37
Active Fault Code
-