Programming
vacon • 19
24-hour s358 (0)201 212 575 • Email: [email protected]
5
5.1
Modbus RS-485 parameters and monitoring values
Table 4. Parameters related with Modbus used through RTU
1)
This feature is not supported in Vacon 100 HVAC. The default Vacon 100 application supports only
Slave mode. A special application is required for Master functionality.
Code
Parameter
Min
Max
Unit
Default
ID
Description
PARAMETERS
P5.X.3.1.1
Slave address
1
247
1
2320 Unique slave device address.
P5.X.3.1.2
Baud rate
300
230400
bd
6
2378
Communication speed
300
600
1200
2400
4800
9600
19200
38400
57600
76800
115200
230400
P5.X.3.1.3
Parity type
0
2
0
2379
0 = Even
1 = Odd
2 = None
P5.X.3.1.4
Stopbits
1
3
3
2380
1 = 1 stop bit
2 = 1.5 stop bits
3 = 2 stop bits
P5.X.3.1.5
Communication
time-out
0
65535
s
10
2321 0 = Not used
P5.X.3.1.6
(1)
Operate Mode
0
1
0
2374
0 = Slave
1 = Master
P5.x.3.1.7.1-30
IDMap IDs
0
65535
0
IDMap IDs
MONITORING VALUES
P5.X.3.2.1
Fieldbus protocol
status
1
3
1
2381
0 = Init
1 = Stopped
2 = Operational
3 = Faulted
P5.X.3.2.2
Communication sta-
tus
0.0
99.999
0.0
2382
0-99 Number of messages
with errors
0-999 Number of messages
without communication
errors
P5.X.3.2.3
Illegal functions
0
2383 See page 23.
P5.X.3.2.4
Illegal data
addresses
0
2384 See page 23.
P5.X.3.2.5
Illegal data values
0
2385 See page 23.
P5.X.3.2.6
Slave device busy
0
2386 See page 23.
P5.X.3.2.7
Memory parity error
0
2387 See page 23.
P5.X.3.2.8
Slave device failure
0
2388 See page 23.
P5.X.3.2.9
Last fault response
0
2389 See page 23.
P5.X.3.2.10
Control word
hex
2390 See page 33 and page 36.
P5.X.3.2.11
Status word
hex
2391 See page 33 and page 36.