ENGLISH
- 32 -
8.3 - ACTIVATION INPUT
The control unit has an activation input (START) for the connection
of a N.O. button.
Connect the cables of the device that controls the START
between terminals
L3 (START)
and
L6 (COM)
C
The operating logic of the START button and of the START
remote control (channel 1 on the receiver) depends on the
settings performed on the following parameters:
St.AP
: Start command during opening phase
(default
=
PAUS
the gate goes in standby)
St.Ch
: Start command during closing phase
(default
=
StoP
the gate stops and the cycle ends)
St.PA
: Start command during Pause
(default
=
Chiu
the gate closes)
L1
L2
L3
L4
L5
L6
L7
L8
L9
L10
L11
The START function can also be enabled by means of a remote
control saved on channel 1 of the MR receiver.
8.4 - CONNECTING PHOTOCELLS
PD22 control unit supplies a 24Vdc power supply to photocells.
Photocell power terminals are protected by an electronic fuse that
stops current in case of overload.
C
The input is disabled by default; to enable it, change the
settings of the
Foto
parameter
• Connect power supply cables of photocells transmitter
between terminals
L8 (COM)
and
L9 (+)
of the control unit.
• Connect power supply cables of photocells receiver between
terminals
L7 (+)
and
L8 (COM)
of the control unit.
• Connect N.C. receiver output between terminals
L6 (COM)
and
L4 (PHOTO)
of the control unit. Use outputs having
normally closed contact.
TX
RX
L1
L2
L3
L4
L5
L6
L7
L8
L9
L10
L11
8.5 - STOP / SAFETY EDGE
The control unit is equipped with a configurable safety input that
can be used to connect a STOP button to a safety edge.
C
The input is disabled by default; to enable it as STOP or
EDGE, you need to change the settings of the
SiC
parameter
STOP button
To connect a STOP button, you need to set the parameter
SiC = StoP
Connect the cables of the STOP button (N.C.) between terminals
L5 (STOP)
and
L6 (COM)
.
Opening the button will cause the motor to stop and will cancel
the automatic closing command (if enabled).
L1
L2
L3
L4
L5
L6
L7
L8
L9
L10
L11
STOP
COM
The STOP function can also be enabled by means of a remote
control saved on channel 3 of the MR receiver.
Safety edge
To connect a safety edge, you need to set the parameter
SiC = EdGE
Connect the cables of the safety edge between terminals
L5 (EDGE)
and
L6 (COM)
.
L1
L2
L3
L4
L5
L6
L7
L8
L9
L10
L11
EDGE
COM
The intervention of the edge during the closing phase will cause
the gate to open completely and will cancel the automatic closing
command (if enabled).
This input can control either the classic edge with N.C. contact,
or the conductive rubber ones with nominal resistance 8,2 kohm.
m
WARNING:
• When using more edges with N.C. contact, the inputs have to
be series connected.
• If using more conductive rubbers, the outputs have to be
cascade connected and only the last one has to be terminated
on the nominal resistance.