![V-TAC SUN-5K-SG04LP3-EU Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/v-tac/sun-5k-sg04lp3-eu/sun-5k-sg04lp3-eu_user-manual_3099863034.webp)
- 32 -
Float V
53.6V
20%
35%
50%
-5
Absorption V
57.6V
Equalization V
57.6V
Equalization Days
Shutdown
Low Batt
Restart
TEMPCO(mV/C/Cell)
Batt Resistance
30 days
Equalization Hours
3.0
hours
25mOhms
Battery Setting
Set3
Batt
①
②
③
Lithium Mode
Shutdown
Low Batt
Restart
40%
20%
10%
00
Battery Setting
Set3
Batt
Lithium Mode:
This is BMS protocol.Please reference
the document(Approved Ba�ery).
Shutdown 10%:
It indicates the inverter will shutdown
if the SOC below this value.
Low Ba� 20%:
It indicates the inverter will alarm if the
SOC below this value.
Restart 40%:
Ba�ery voltage at 40% AC output will
resume.
This page tells generator output voltage, frequency,
power. And, how much energy is used from generator.
Power: 6000W
Today=10 KWH
Total =10 KWH
Generator
V_L1: 230V
V_L2: 230V
V_L3: 230V
P_L1: 2KW
P_L2: 2KW
P_L3: 2KW
There are 3 stages of charging the Ba�ery .
①
②
This is for professional installers, you can keep it
if you do not know.
Shutdown 20%:
The inverter will shutdown if the SOC
below this value.
Low Ba� 35%:
The inverter will alarm if the SOC
below this value.
Restart 50%:
Ba�ery SOC at 50% AC output will resume.
③
Recommended ba�ery se�ngs
Battery Type
AGM (or PCC)
Absorption Stage
14.2V (57.6V)
13.4V (53.6V)
Float Stage
Torque value
(every 30 days 3hr )
14.2V(57.6V)
Gel
14.1V (56.4V)
13.5V (54.0V)
Wet
14.7V (59.0V)
13.7V (55.0V)
14.7V(59.0V)
Lithium
Follow its BMS voltage parameters