5.6 Ba�ery Setup Menu
Batt Mode
Lithium
Use Batt V
Battery Setting
Activate Battery
Max A Charge
Batt Capacity
Max A Discharge
40A
40A
400Ah
Batt
Mode
Use Batt %
No Batt
Ba�ery capacity:
it tells hybrid inverter to know
your ba�ery bank size.
Use Ba� V:
Use Ba�ery Voltage for all the se�ngs (V).
Use Ba� %:
Use Ba�ery SOC for all the se�ngs (%).
Max. A charge/discharge:
Max ba�ery charge/discharge
current(0-120A for 5kW model, 0-150A for 6kW model,
0-190A for 8kW model, 0-210A for 10kW model, 0-240A
for 12kW model).
For AGM and Flooded, we recommend Ah ba�ery
size x 20%= Charge/Discharge amps.
. For Lithium, we recommend Ah ba�ery size x 50% =
Charge/Discharge amps.
. For Gel, follow manufacturer' s instruc�ons.
No Ba�:
�ck this item if no ba�ery is connected
to the system.
Ac�ve ba�ery:
This feature will help recover a
ba�ery that is over discharged by slowly charging
from the solar array or grid.
This is Ba�ery Setup page.
Start =30%:
Percent S.O.C at 30% system will AutoStart a
connected generator to charge the ba�ery bank.
A = 40A:
Charge rate of 40A from the a�ached
generator in Amps.
Gen Charge:
uses the gen input of the system to charge
ba�ery bank from an a�ached generator.
Gen Signal:
Normally open relay that closes when the
Gen Start signal state is ac�ve.
①③
Start =30%:
No use
,
Just for customiza�on.
A = 40A:
It indicates the Current that the
Grid charges the Ba�ery.
Grid Charge:
It indicates that the grid charges
the ba�ery.
Grid Signal:
Disable.
This is Grid Charge, you need select.
②
07/08/2021 11:11:10 Thu
76%
2.00
KW
-1.39
KW
0.00
KW
KW
0
7
0
5
0
5
0
5
ON
Signal
on
2.00
This page tells the PV and diesel generator
power the load and ba�ery.
Grid Charge
Gen Charge
Grid Signal
Gen Signal
Gen Max Run Time
24.0 hours
Gen Down Time
0.0 hours
Battery Setting
Start
A
30%
30%
40A
40A
Batt
Set2
①
②
③
Gen Max Run Time:
It indicates the longest �me
Generator can run in one day, when �me is up, the
Generator will be turned off. 24H means that it does
not shut down all the �me.
Gen Down Time:
It indicates the delay �me of the
Generator to shut down a�er it has reached the running
�me.