Level limit switch
Series RF 8000
Technical Information / Instruction manual
page
Operation - Electronic module: Standard
General applications
Switchpoint Adjustment
Application
Material
Adjustment conditions
General
• Dry solids
• Low viscosity liquids
Sensor uncovered
Demanding
• Hygroscopic / wet solids
• High viscosity and high conductivity liquids
Sensor immersed and then uncovered, retaining
max. possible material buildup
Interface
detection
• Ignoring liquid A / detecting liquid B
• Ignoring foam / detecting liquid
Immerse sensor in liquid A or foam
Select the switchpoint adjustment according to the application as follows:
1. Ensure material level is
well below the probe
The unit will calibrate to an uncovered probe.
2. Set to high sensitivity
Set dip switch S5 to high sensitivity
3. Adjust switchpoint
with poti P2
If LED L1 (yellow) is OFF,
turn poti P2 counter clockwise until L1 is ON.
Turn P2 clockwise until L1 just stops glowing.
Turn P2 further clockwise:
Dielectric constant
of material
Number of
turns
< 2
1/8
2 ... 4
1/4
> 4
1/2
Depending on the application and the required
switchpoint the number of turns can be varied.
Switchpoint adjustment is
finished
P2
L1