Level limit switch
Series RF 8000
Technical Information / Instruction manual
Operation - Electronic module: Standard
Allows to test the setted signal output delay time without the need to change the sensor from covered to uncovered or
from uncovered to covered.
S4
Normal
operation*
S4
Test mode
If sensor is
uncovered
:
Setting S4 to Test mode simulates a
covered
probe. After the setted delay time
"Sensor uncovered to covered" (see DIP switch S2) has passed, the signal output and
LED2 (red) are switching.
If sensor is
covered
:
Setting S4 to Test mode simulates a
uncovered
probe. After the setted delay time
"Sensor covered to uncovered" (see DIP switch S1) has passed, the signal output and
LED2 (red) are switching.
S4: Test
*Factory setting
*Factory setting
S5: Sensitivity setting
S5
Low
sensitivity
This setting is prefered for measuring conductive liquids, or viscous conductive solids
that can build up on the sensor.
S5
High
sensitivity*
Use this setting for measuring dry solids or nonconductive liquids.
1
2
3
4
5
6
7
8
9
10
11
12
RF 8000 c
gi150917
25
RFnivo
®