NivoRadar
®
Continuous level measurement
Series NR 7100
Technical information / Instruction manual
Mounting
page 17
1
Fig. 8: Position of the polarisation
1 Marking of the polarisation
Note:
When the housing is rotated, the direction of polarization changes
and hence the influence of the false echo on the measured value.
Please keep this in mind when mounting or making changes later.
When mounting the device, keep a distance of at least 200 mm
(7.874 in) from the vessel wall. If the device is installed in the center
of dished or round vessel tops, multiple echoes can arise. However,
these can be suppressed by an appropriate adjustment (see chapter
" Set up").
If you cannot maintain this distance, you should carry out a false
signal suppression during setup. This applies particularly if buildup
on the vessel wall is expected. In such cases, we recommend
repeating the false signal suppression at a later date with existing
buildup.
> 200 mm
(7.87")
Fig. 9: Mounting of the radar sensor on round vessel tops
In vessels with conical bottom it can be advantageous to mount the
device in the centre of the vessel, as measurement is then possible
down to the bottom.
Installation position