45
NivoGuide® 8100 • Two-wire 4 … 20 mA/HART
7 Diagnostics and servicing
58878-EN-190215
This status message is inactive by default.
Maintenance: Due to external influences, the instrument function
is limited. The measurement is affected, but the measured value is
still valid. Plan in maintenance for the instrument because a failure is
expected in the near future (e.g. due to buildup).
This status message is inactive by default.
Code
Text mes-
sage
Cause
Rectification
DevSpec State in CMD 48
F013
no measured
value avail-
able
•
Sensor does not detect an
echo during operation
•
Process component or probe
contaminated or defective
•
Check for correct mounting
and/or parameter settings
•
Clean or exchange process
component or probe
Bit 0 of Byte 0 … 5
F017
Adjustment
span too small
•
Adjustment not within specifi
-
cation
•
Change adjustment accord-
ing to the limit values (differ
-
ence between min. and max.
≥ 10 mm)
Bit 1 of Byte 0 … 5
F025
Error in the
linearization
table
•
Index markers are not con-
tinuously rising, for example
illogical value pairs
•
Check values of the lineari-
zation table
•
Delete/create a new lineari-
zation table
Bit 2 of Byte 0 … 5
F036
No operable
software
•
Failed or interrupted software
update
•
Repeat software update
•
Check electronics version
•
Exchanging the electronics
•
Send instrument for repair
Bit 3 of Byte 0 … 5
F040
Error in the
electronics
•
Hardware defect
•
Exchanging the electronics
•
Send instrument for repair
Bit 4 of Byte 0 … 5
F041
Probe loss
•
Probe mechanically defec-
tive
•
Check probe and exchange,
if necessary
Bit 13 of Byte 0 … 5
F080
General soft-
ware error
•
General software error
•
Disconnect operating voltage
briefly
Bit 5 of Byte 0 … 5
F105
Measured
value is deter-
mined
•
The instrument is still in the
start phase, the measured
value could not yet be
determined
•
Wait for the end of the
switch-on phase
•
Duration depending on
the version and parameter
adjustment max. 5 min.
Bit 6 of Byte 0 … 5
F260
Error in the
calibration
•
Error in the calibration car-
ried out in the factory
•
Error in the EEPROM
•
Exchanging the electronics
•
Send instrument for repair
Bit 8 of Byte 0 … 5
F261
Error in the
instrument
settings
•
Error during setup
•
Error when carrying out a
reset
•
False signal suppression
faulty
•
Carry out a reset
•
Repeat setup
Bit 9 of Byte 0 … 5
Failure
Содержание NivoGuide 8100
Страница 72: ...72 NivoGuide 8100 Two wire 4 20 mA HART INDEX 58878 EN 190215 U Units 26 ...
Страница 73: ...73 NivoGuide 8100 Two wire 4 20 mA HART Notes 58878 EN 190215 ...
Страница 74: ...74 NivoGuide 8100 Two wire 4 20 mA HART Notes 58878 EN 190215 ...
Страница 75: ...75 NivoGuide 8100 Two wire 4 20 mA HART Notes 58878 EN 190215 ...