NivoGuide® 8100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module
58878-EN-190215
Menu
Menu item
Default value
Setup
Current output, output variable
Lin. percent - Level
Current output - Output characteristics
0 … 100 % correspond to
4 … 20 mA
Current output - Reaction in case of fault
≤ 3.6 mA
Current output - Min.
3.8 mA
Current output - Max.
20.5 mA
Current output 2 - Output variable
Distance - Level
Current output 2 - Output characteristics
0 … 100 % correspond to
4 … 20 mA
Current output 2 - Reaction in case of fault
≤ 3.6 mA
Current output 2 - Min.
3.8 mA
Current output 2 - Max.
20.5 mA
Menu - Display
Menu
Menu item
Default value
Display
Language
Selected language
Displayed value 1
Filling height
Displayed value 2
Electronics temperature
Display format 1
Automatically
Display format 2
Automatically
Backlight
Switched on
Menu - Additional adjustments
Menu
Menu item
Default value
Additional adjustments PIN
0000
Date
Actual date
Time
Actual time
Time - Format
24 hours
Probe type
Device-specific
The instrument settings are copied with this function. The following
functions are available:
•
Read from sensor: Read data from sensor and save in the display
and adjustment module
•
Write to sensor: Save data from the display and adjustment mod-
ule back into the sensor
The following data or settings for adjustment of the display and ad-
justment module are saved:
•
All data of the menu "
Setup
" and "
Display
"
•
In the menu "
Additional adjustments
" the items "
Reset, Date/Time
"
Additional settings - Copy
instrument settings
Содержание NivoGuide 8100
Страница 72: ...72 NivoGuide 8100 Two wire 4 20 mA HART INDEX 58878 EN 190215 U Units 26 ...
Страница 73: ...73 NivoGuide 8100 Two wire 4 20 mA HART Notes 58878 EN 190215 ...
Страница 74: ...74 NivoGuide 8100 Two wire 4 20 mA HART Notes 58878 EN 190215 ...
Страница 75: ...75 NivoGuide 8100 Two wire 4 20 mA HART Notes 58878 EN 190215 ...