NivoGuide® 8100 • Two-wire 4 … 20 mA/HART
6 Set up with the display and adjustment module
58878-EN-190215
With the following functions you can zoom part sections of the echo
curve.
•
"X-Zoom": Zoom function for the meas. distance
•
"Y-Zoom": 1, 2, 5 and 10x signal magnification in "
V
"
•
"Unzoom": Reset the presentation to the nominal measuring range
without magnification
In this menu item you can simulate measured values via the current
output. This allows the signal path to be tested, e.g. through down-
stream indicating instruments or the input card of the control system.
Select the requested simulation variable and set the requested value.
Caution:
During simulation, the simulated value is output as 4 … 20 mA current
value and digital HART signal.
Push the
[ESC]
key to deactivate the simulation.
Information:
The simulation is terminated automatically 60 minutes after the activa-
tion of the simulation.
With the menu item "
Setup
" the echo curve it is possible to save at
the time of setup. This is generally recommended; for using the Asset
Management functions it is necessary. If possible, the curve should
be saved with a low level in the vessel.
This allows you to detect signal changes over the operating time.
The function "
Echo curve memory
" enables storing echo curves of
the measurement.
Under the sub-menu item "
Echo curve memory
" you can store the
current echo curve.
Diagnosis - Simulation
Diagnostics - Echo curve
memory
Содержание NivoGuide 8100
Страница 72: ...72 NivoGuide 8100 Two wire 4 20 mA HART INDEX 58878 EN 190215 U Units 26 ...
Страница 73: ...73 NivoGuide 8100 Two wire 4 20 mA HART Notes 58878 EN 190215 ...
Страница 74: ...74 NivoGuide 8100 Two wire 4 20 mA HART Notes 58878 EN 190215 ...
Страница 75: ...75 NivoGuide 8100 Two wire 4 20 mA HART Notes 58878 EN 190215 ...