Product Description

The Jack Jumper™ Cutout Bypass Tool permits a safe and quick method to bypass 

an overhead cutout without the tedious use of bulky jumper cables.  The tool is 

indispensable for fuse coordination tasks and permits easy bypass of an underground 

dip.  The Jack Jumper™ Cutout Bypass Tool saves time and money, eliminates risk of 

service interruption and prevents accidental cross phasing.
The primary purpose of the Jack Jumper™ Cutout Bypass Tool is to provide temporary 

fuse replacement when performing fuse coordination on cutouts. The Jack Jumper™ 

Cutout Bypass Tool is rated at 100 Amps continuous on AC current without exceeding 

a 40°C temperature rise. It is used to bypass cutouts on both overhead lines and 

underground taps. For 200 Ampere SMD-20 systems attach two Jack Jumper™ Cutout 

Bypass Tools on opposite sides of the SMD-20 Power Fuse (this only works for SMD-20 

Power Fuse Tools and cannot be utilized for standard cutouts). 
Installation and removal of the  Jack Jumper™ Cutout Bypass Tool is done with a 

shotgun stick.

Product Line

USJJ-001 15 kV Cutout Bypass Tool

USJJ-002 27 kV Cutout Bypass Tool

USJJ-003 15 kV Chance™ Loadbreak Cutout Bypass Tool

USJJ-004 15 kV ABB™ Loadbreak Cutout Bypass Tool

USJJ-005 38kV Cutout & S&C™ SMD-20 15 kV Power Fuse Bypass Tool
USJJ-006 S&C™ SMD-20 27 kV Power Fuse Bypass Tool

USJJ-007 S&C™ SMD-20 38 kV Power Fuse Bypass Tool

USJJ-008 27 kV Chance™ Loadbreak Cutout Bypass Tool

USJJ-009 27kV ABB™ Loadbreak Cutout Bypass Tool

Top Perpendicular 

Ring

Spring Mechanism

Bottom In-Line Ring

Upper 

Attachment Hook

Lower

Attachment Hook

Содержание Jack Jumper SMD-20

Страница 1: ...ss Tool C 00829 USJJ 005 Manual Rev 6 5 8 15 14 USJJ 005 38 kV Cutout Bypass Tool 15 kV SMD 20 Power Fuse Bypass Tool Operation Maintenance Manual Contents Product Description 4 Product Line 4 Safety...

Страница 2: ...an result in death grievous personal injury and or equipment damage WARNING Follow safe work procedures and practices when utilizing this device Failure to use this device in a safe manner can result...

Страница 3: ...is used to bypass cutouts on both overhead lines and underground taps For 200 Ampere SMD 20 systems attach two Jack Jumper Cutout Bypass Tools on opposite sides of the SMD 20 Power Fuse this only wor...

Страница 4: ...lace It is not a switch and should never be used as one If emergency arises follow the standard safety operating procedures for your facility The Jack Jumper Cutout Bypass Tool should be stretched sli...

Страница 5: ...utout Figure A 4 Be sure the Jack Jumper Cutout Bypass Tool is secure and will not interfere with removal of the fuse 5 Release the top ring 6 Grasp the bottom in line ring of the Jack Jumper Cutout B...

Страница 6: ...r Cutout Bypass Tool with the shotgun stick 7 Gently pull to expand the spring and hook the bottom attachment hook on the lower fuse door hinge casting Figure D The Jack Jumper Cutout Bypass Tool is n...

Страница 7: ...ntenance disassembly or misuse voids any and all warranties guarantees or liability Warranty Utility Solutions warrants the Jack Jumper Cutout Bypass Tool for any defects in manufacturing for the peri...

Страница 8: ...8 C 00829 USJJ 005 Manual Rev 6 5 8 15 14...

Отзывы: