General Information
P/N 06-237214-002
1-7
June 2012
1-3.3
Light Emitting Diodes (LEDs)
LEDs are included on the ProtoCessor board (see Figure 1-6) and the Main Board (Figure 1-7).
Refer to Table 1-3 (ProtoCessor LEDs) and Table 1-4 (Main LEDs) for a brief description of LED
functionality.
Figure 1-6. LEDs on BACnet Interface Module ProtoCessor Board
Table 1-3. ProtoCessor Board LED Functionality
Power
Unused
Run
Sys Err
Comm Err
Config Err
Node Offline
RX
TX
Light
Description
PWR
This
is
the
power
light
and
should
show
steady
green
at
all
times
when
the
module
is
powered.
SYS
ERR
The
SYS
ERR
LED
will
go
on
solid
15
seconds
after
power up.
It
will
turn
off
after
5
seconds.
A
steady
red
light
will
indicate
there
is
a
system
error
on
the
module.
If
this
occurs,
immediately
report
the
related
“system
error”
shown
in
the
error
screen
of
the
RUI
interface
to
Fenwal
Protection
Systems
Technical
Support
for
evaluation.
COMM
ERR
COMM
ERR
LED
will
go
on
solid
15
seconds
after
power
up.
It
will
turn
off
after
5
seconds.
A
steady
red
light
will
indicate
a
communication
error
has
occurred.
To
establish
the
cause
of
the
error,
go
to
the
error
screen
of
the
RUI
interface.
Config
ERR
Config
ERR
LED
will
go
on
solid
15
seconds
after
power
up.
It
will
turn
off
after
5
seconds.
A
steady
amber
light
will
indicate
a
configuration
error
exists
in
the
active
configuration.
See
the
Error
Screen
in
the
Remote
User
Interface
for
a
description
of
the
configuration
error.
Node
Offline
Node
Offline
LED
will
go
on
solid
15
seconds
after
power
up.
It
will
turn
off
after
5
seconds.
If
the
Node
Offline
LED
stays
on
solid,
a
Node
Offline
condition
has
occurred.
Unused
15
seconds
after
powering
up
the
4
unused
LEDs
will
turn
on
solid
for
5
seconds
and
then
turn
off.
RX
On
normal
operation,
the
RX
LED
will
flash
when
a
message
is
received
on
the
field
port
of
the
module.
TX
On
normal
operation,
the
TX
LED
will
flash
when
a
message
is
sent
on
the
field
port
of
the
module.
RUN
RUN
LED
will
flash
20
seconds
after
power
up,
signifying
normal
operation.
The
module
will
be
able
to
access
RUINET
once
this
LED
starts
flashing.
During
the
first
20
seconds,
the
LED
should
be
off.