Remote Booster Power Supply Technical Reference Manual
51
Genesis visible circuit and conventional audible circuit
to Genesis notification
Figure 34: Genesis visible circuit and conventional audible circuit to Genesis notification
G
G
G
G
G
G
G
G
G
(11)
(12)
(12)
G
G
G
G
G
G
G
G
(1)
(2)
(3)
(4)
BPS
(7)
(8)
(9)
(10)
(5)
(6)
(3)
(4)
BPS
(7)
(8)
(9)
(10)
(5)
(6)
(1) NAC visible circuit
(2) NAC audible circuit
(3) Sense 1
(4) Sense 2
(5) Mode: GM
(6) NACs: SF
(7)
NAC1
(8) NAC 2
(9) NAC
3
(10) NAC 4
(11) To next BPS, or EOL resistor
(12) To next device or EOL resistor
Note: The maximum number of BPSs that can be connected on a single NAC from sense circuit
to sense circuit is limited by available current and wire run length.
DIP switch settings for this application
BPS DIP switches can be set this way for the application to work correctly. Refer
to “Setting the DIP switches” for other options.
Figure 35: Switch settings
SW1
SW2
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8