Remote Booster Power Supply Technical Reference Manual
35
Battery calculation worksheet
Supervisory (AUX1, AUX2, AUX3, AUX4)
Note: Only add auxiliary current if SW2-7 is OFF. Auxiliary output stays on
after AC power failure.
Device type
Quantity
Current (mA)
Total/device
Total AUX current (0 if switch SW2-7 is off, maximum 6.5 A
for BPS6A and 8 A for BPS10A):
mA
(A)
Number of circuits set to
AUX
35 mA (per AUX
circuit)
mA
(B)
200 mA AUX
Device type
Quantity
Current (mA)
Total/device
Total 200 mA AUX current:
mA (C)
Rated base BPS supervisory current:
70 mA (D)
Total supervisory current (A + B + C + D):
mA (E)
Hours of supervisory:
Hrs (F)
Supervisory mAh (E x F):
mAh (G)
Alarm (NAC1, NAC2, NAC3, NAC4)
Device type
Quantity
DC current (mA,
RMS)
Total/device
Total NAC current:
mA (H)
Rated base BPS alarm current:
270 mA (J)
Total alarm current (E + H + J):
mA (K)
Minutes of alarm:
Min (L)
Hours of alarm (L/60):
Hr (M)