Remote Booster Power Supply Technical Reference Manual
31
Legend
(1) NAC1/AUX1
(2) NAC2/AUX2
(3) NAC3/AUX3
(4) NAC4/AUX4
(5)
200 mA AUX Continuous
(6) Sense 1 IN
(7) Sense
1
COM
(8) Sense
1
OUT
(9) Sense 2 IN
(10) Sense
2
COM
(11) Sense
2
OUT
(12) Trouble NO
(13) Trouble
COM
(14) Trouble
NC
(15) Notification appliance circuit (NAC)
(16) UL listed EOL 15 k
Ω
(17) EOL 47 k
Ω
(18) Data in from previous device or
Signature controller
(19) Data out to next device
Notes
•
CC1(S) modules must be wired and programmed on the Signature controller for proper
operation.
•
Any BPS trouble causes the CC1(S) supervision to report a trouble to the main control panel
when DIP switch SW2-6 is on. AC power failure is delayed for three hours.
•
If CC1(S) wiring is more than three feet from a BPS enclosure, then a separate listed EOL
relay (PAM1, 6254A-003, or 73402A) or equivalent must be used to supervise the 200 mA
AUX circuit wiring.
•
When configured for AC power loss reporting using the trouble relay (DIP switch SW2-6 ON),
the CT1 module supervises and reports the AC power.