IMPORTANT
Be sure to read and understand the entire
instruction manual before installing or operating
the flame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.
ATTENTION
The X2200 includes the Automatic Optical Integrity
(
oi
®
) feature — a calibrated performance test that
is automatically performed once per minute to
verify complete detector operation capabilities.
No
testing with an external test lamp is required.
DESCRIPTION
The evolution continues with the new X2200 UV
Flame Detector. The X2200 meets the most stringent
requirements worldwide with advanced detection
capabilities and immunity to extraneous sources,
combined with a superior mechanical design. The
detector is equipped with both automatic and manual
oi
test capability. The detector has Division and Zone
explosion-proof ratings and is suitable for use in indoor
and outdoor applications.
The standard output configuration includes fire, fault and
auxiliary relays. Output options include:
–
0 to 20 mA output (in addition to the three relays)
–
Pulse output for compatibility with existing controller
based systems (with fire and fault relays)
–
Eagle Quantum Premier® (EQP) compatible model
(no analog or relay outputs)
–
HART Communication
A tricolor LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm or
fault conditions.
The X2200 housing is available in copper-free aluminum
or stainless steel, both with NEMA 4X and IP66 rating.
OUTPUTS
Relays
The standard detector is furnished with fire, fault and
auxiliary relays. All three relays are rated 5 amperes at
30 Vdc.
The Fire Alarm relay has redundant terminals and normally
open / normally closed contacts, normally de-energized
operation, and latching or non-latching operation.
The Fault relay has redundant terminals and normally
open contacts, normally energized operation, and
latching or non-latching operation.
INSTRUCTIONS
UV Flame Detector
X2200
8.3
©
Detector Electronics Corporation 2010
Rev: 6/10
95-8549