95-8549

16

8.3

FEATURES

•  Responds to a fire in the presence of modulated 

blackbody radiation (i.e. heaters, ovens, turbines) 

without false alarm.

•  High speed capability.
•  Built-in data logging / event monitoring, up to 1500 

events (up to 1000 general, 500 alarms).

•  Automatic, manual or magnetic optical integrity (

oi

testing.

•  Easily replaceable 

oi

 plate.

•  Fire, fault and auxiliary relays standard.
•  0 to 20 mA isolated output (optional).
•  Eagle Quantum Premier LON/SLC output (optional).
•  A tricolor LED on the detector faceplate indicates 

normal condition and notifies personnel of fire alarm 

or fault conditions.

•  Operates under adverse weather conditions.
•  Mounting swivel allows easy sighting.
•  Integral wiring compartment for ease of installation.
•  Explosion-proof/flame-proof detector housing.  Meets 

FM, CSA, ATEX and CE certification requirements.

•  Class A wiring per NFPA-72.
•  Meets NFPA-33 response requirement for under 

0.5 second (available when model selected).

•  3 year warranty.
•  Advanced signal processing (ARC).
•  RFI and EMC Directive compliant.

ASSOCIATED MANUALS

List of X2200 related manuals:

TITLE

FORM NUMBER

Pulse

95-8552

EQP

95-8533

HART Addendum

95-8638

SPECIFICATIONS

OPERATING VOLTAGE—  

24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum).  

Maximum ripple is 2 volts peak-to-peak.

POWER CONSUMPTION—

 

2.5 watts at 24 Vdc nominal;

 

  4.5 watts at 24 Vdc in alarm.

 

2.8 watts at 30 Vdc nominal;

 

  5.1 watts at 30 Vdc in alarm.

Total power:  7.6 watts at 30 Vdc with EOL resistor 

installed.

EOL resistor must be ceramic, wirewound type, rated 

5 watts minimum, with actual power dissipation not to 

exceed 2.5 watts.

For HART model, refer to Addendum number 95-8638.

POWER UP TIME—

Fault indication clears after 0.5 second; device is ready 

to indicate an alarm condition after 30 seconds.

OUTPUT RELAYS—

Fire Alarm relay,  Form C, 5 amperes at 30 Vdc:

 

The Fire Alarm relay has redundant terminals 

and normally open / normally closed contacts, 

normally de-energized operation, and latching or 

non-latching operation.

Fault relay, Form A, 5 amperes at 30 Vdc:

 

The Fault relay has redundant terminals and 

normally open contacts, normally energized 

operation, and latching or non-latching operation.

Auxiliary relay,  Form C, 5 amperes at 30 Vdc:

 

The auxiliary relay has normally open / normally 

closed contacts, normally energized or de-energized 

operation, and latching or non-latching operation.

CURRENT OUTPUT (Optional)—

0 to 20 milliampere (±0.3 mA) dc current, with a 

maximum loop resistance of 500 ohms from 18 to 

19.9 Vdc and 600 ohms from 20 to 30 Vdc.

LON OUTPUT—

Digital communication, transformer isolated (78.5 kbps).

TEMPERATURE RANGE—

Operating:  –40°F to +167°F  (–40°C to +75°C).

Storage: 

–67°F to +185°F (–55°C to +85°C).

Hazardous location ratings from –55°C to +75°C available 

on flameproof model.

HUMIDITY RANGE—

0 to 95% relative humidity, can withstand 100% 

condensing humidity for short periods of time.

Содержание Det-Tronics X2200

Страница 1: ...Instructions 95 8549 UV Flame Detector X2200 8 3 Rev 6 10 95 8549 ...

Страница 2: ...6 Detector Orientation 6 Protection Against Moisture Damage 6 Wiring Procedure 7 EOL Resistors 8 Setting Device Network Addresses EQ and EQP Models Only 13 STARTUP PROCEDURE 14 Fire Alarm Test 14 TROUBLESHOOTING 14 MAINTENANCE 15 Cleaning Procedure 15 oi Plate Removal 15 Periodic Checkout Procedure 15 Clock Battery 15 FEATURES 16 SPECIFICATIONS 16 REPLACEMENT PARTS 19 DEVICE REPAIR AND RETURN 19 O...

Страница 3: ...door applications The standard output configuration includes fire fault and auxiliary relays Output options include 0 to 20 mA output in addition to the three relays Pulse output for compatibility with existing controller based systems with fire and fault relays Eagle Quantum Premier EQP compatible model no analog or relay outputs HART Communication A tricolor LED on the detector faceplate indicat...

Страница 4: ...es personnel of fire alarm or fault conditions Table 2 indicates the condition of the LED for each status OPTICAL INTEGRITY oi Automatic oi The X2200 includes the Automatic Optical Integrity oi feature a calibrated performance test that is automatically performed once per minute to verify complete detector operation capabilities No testing with an external test lamp is required The detector automa...

Страница 5: ...e and date stamped along with the temperature and input voltage Event data is stored in non volatile memory when the event becomes active and again when the status changes Data is accessible using the RS 485 port or the EQP controller INTEGRAL WIRING COMPARTMENT All external wiring to the device is connected within the integral junction box The screw terminals accept wiring from 14 to 24 AWG The d...

Страница 6: ...olar radiation However it will respond to sources of UV besides fire such as electric arc welding lightning high voltage corona x rays and gamma radiation FACTORS INHIBITING DETECTOR RESPONSE Windows Glass and Plexiglas windows significantly attenuate UV radiation and must not be located between the detector and a potential flame source If the window cannot be eliminated or the detector location c...

Страница 7: ...r before activating the system ATTENTION Observe precautions for handling electrostatic sensitive devices The following is a partial list of compounds that exhibit significant UV absorption characteristics These are also usually hazardous vapors While generally of little consequence in small amounts these gases can restrict UV detection if they are in the atmosphere in heavy concentrations It shou...

Страница 8: ...UV radiation and reduce the sensitivity of the detector Verify that all detectors in the system are properly aimed at the area to be protected The Det Tronics Q1201C Laser Aimer is recommended for this purpose If possible fire tests should be conducted to verify correct detector positioning and coverage For ATEX installations the X2200 detector housing must be electrically connected to earth groun...

Страница 9: ...ed cable is recommended Wires should be stripped 3 8 inch 9 mm A minimum input voltage of 18 Vdc must be present at the X2200 NOTE Refer to Power Consumption in the Specifications section of this manual The use of shielded cable is required to protect against interference caused by EMI and RFI When using cables with shields terminate the shields as shown in Figures 7 through 12 and Figure 14 Consu...

Страница 10: ...s must be ceramic wirewound type rated 5 watts minimum with actual power dissipation not to exceed 2 5 watts This applies to ATEX IEC installations only 2 Resistor leads should be cut to a length of approximately 1 1 2 inches 40 mm 3 Bend the leads and install the EOL resistor as shown in Figure 6 4 Maintain a 3 8 inch 10 mm minimum gap between the resistor body and the terminal block or any other...

Страница 11: ...6 25 24 23 22 21 SPARE SPARE RS 485 A RS 485 B MAN Oi 4 20 mA 4 20 mA 4 20 mA REF 4 20 mA REF COM AUX N O AUX N C AUX Figure 7 Ex d Wiring Option B2152 FIRE ALARM PANEL X2200 DETECTOR ALARM ALARM 24 VDC WIRING NOTES 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING THE FAULT RELAY COIL IS ENERGIZED AND THE NORMALLY OPEN N O AND COMMON COM CONTACTS ARE CLOSED 2 ALARM RELAY IS NORMALLY DE ENERGIZED WIT...

Страница 12: ... mA Current Output Sinking 24 VDC 4 TO 20 mA PLC 600 Ω MAX AT 24 VDC C2155 Oi TEST1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 4 20 mA 4 20 mA 29 28 27 26 25 24 23 22 21 MAN Oi X2200 DETECTOR 24 VDC 24VDC 24VDC 24VDC Figure 11 X2200 Detector Wired for Isolated 0 to 20 mA Current Output Sourcing 24 VDC 4 TO 20 mA PLC 600 Ω MAX AT 24 VDC C2156 Oi TEST1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 ...

Страница 13: ...dresses section of this manual for switch setting procedure 5 Check all field wiring to be sure that the proper connections have been made 6 Replace the device cover 7 Make the final sighting adjustments and ensure that the mounting bracket hardware is tight NOTE Refer to the Eagle Quantum Premier system manual number 95 8533 for information regarding power and network communication cable requirem...

Страница 14: ...2 COM1 P1 P2 P3 P4 IN OUT B B COMMON C C SUPPLY A A CH 1 CH 5 IN OUT B B COMMON C C SUPPLY A A CH 2 CH 6 IN OUT B B COMMON C C SUPPLY A A CH 3 CH 7 IN OUT B B COMMON C C SUPPLY A A CH 4 CH 8 CONTROLLER 24 VDC 4 2 24 VDC 3 1 B 52 49 A 53 50 TxD A 59 56 RxD B 58 55 GND GND 57 54 SHIELD 51 48 COM2 COM1 P1 P7 P9 P8 P4 P5 1 5 5 13 1 5 6 14 2 6 7 15 2 6 8 16 3 7 9 17 3 7 10 18 4 8 11 19 4 8 12 20 P2 P3 ...

Страница 15: ...ess to the network address switches For hazardous areas the area must be de classified before attempting disassembly of the device Always observe precautions for handling electrostatic sensitive devices The address number is binary encoded with each switch having a specific binary value with switch 1 being the LSB Least Significant Bit See Figure 16 The device s LON address is equal to the added v...

Страница 16: ...windows 3 Check input power to the unit 4 If the fire system has a logging function check the fire panel log for output status information See Table 4 for information regarding 0 to 20 mA output 5 Turn off the input power to the detector and check all wiring for continuity Important Disconnect wiring at the detector before checking system wiring for continuity 6 If all wiring checks out and cleani...

Страница 17: ...plate following the procedure described below oi PLATE REMOVAL 1 Disable any extinguishing equipment that is connected to the unit 2 Loosen the two captive screws then grasp the oi plate by the visor and remove it from the detector See Figure 17 3 Thoroughly clean the oi plate reflective surfaces holding it by its edges to avoid leaving fingerprints on the inside reflective surface 4 Re install th...

Страница 18: ...at 24 Vdc in alarm 2 8 watts at 30 Vdc nominal 5 1 watts at 30 Vdc in alarm Total power 7 6 watts at 30 Vdc with EOL resistor installed EOL resistor must be ceramic wirewound type rated 5 watts minimum with actual power dissipation not to exceed 2 5 watts For HART model refer to Addendum number 95 8638 POWER UP TIME Fault indication clears after 0 5 second device is ready to indicate an alarm cond...

Страница 19: ...ended Important 18 Vdc minimum must be available at the detector For ambient temperatures below 10 C and above 60 C use field wiring suitable for both minimum and maximum ambient temperature THREAD SIZE Conduit connection Four entries 3 4 inch NPT or M25 Conduit seal not required SHIPPING WEIGHT Approximate Aluminum 6 pounds 2 75 kilograms Stainless Steel 10 pounds 4 5 kilograms Swivel Mount AL 6 ...

Страница 20: ...ble entry devices and blanking elements shall be certified to E generation or ATEX standards in type of explosion protection increased safety e or flameproof enclosure d as applicable suitable for the conditions of use and correctly installed They shall maintain the degree of ingress protection IP66 for the apparatus Unused apertures shall be closed with suitable blanking elements NOTE For ATEX in...

Страница 21: ...01 1 oz grease for detectors non silicon 006097 001 Q1201 Laser 007240 001 Q1116A1001 Air Shield AL 007255 001 Q1201C1001 X Series Laser Holder AL Plastic 007290 001 Q9033B Stainless Steel Swivel Mount Assembly is for aluminum and stainless steel detectors 007290 002 Q9033A Aluminum Swivel Mount Assembly is for aluminum detectors only 007307 001 oi plate for X3301 requires inspector connector to c...

Страница 22: ...E THREAD TYPE 4M 4 PORT METRIC M25 4N 4 PORT 3 4 NPT TYPE OUTPUTS 11 Relay 13 Relay and 4 20 mA 14 Eagle Quantum Premier EQP 15 Relay and Pulse 16 Addressable Module Only Third Party Type 23 HART Relay and 4 20 mA 24 Eagle Quantum TYPE APPROVAL AGENCY W FM CSA ATEX CE IECEx TYPE CLASSIFICATION 1 Division Zone Ex d e 2 Division Zone Ex d Detectors are always Class I Div 1 ...

Страница 23: ...s a calibrated Automatic Optical Integrity oi test for each sensor Upon removal of the contamination the detector fault was cleared and the detector was verified to detect a fire The Manual Magnetic oi performs the same calibrated test as the Automatic oi and additionally actuates the alarm relay to verify output operation If there is a 50 loss of its detection range an alarm signal is not generat...

Страница 24: ... unmodulated 3 0 9 1 x 1 foot n Heptane 75 22 9 1 300 w incandescent lamp modulated unmodulated 3 0 9 1 x 1 foot n Heptane 75 22 9 1 1500 w electric radiant heater modulated unmodulated 10 3 1 x 1 foot n Heptane 75 22 9 1 2 34 w fluorescent lamps modulated unmodulated 3 0 9 1 x 1 foot n Heptane 75 22 9 1 False Alarm Source Distance feet m Modulated Response Unmodulated Response Sunlight direct mod...

Страница 25: ... 1 Standard n Heptane 1 x 1 foot 30 9 1 45 45 1 1 45 30 1 1 Hi Arc n Heptane 1 x 1 foot 30 9 1 45 45 2 2 45 30 2 2 Very Hi Arc Methane 32 inch plume 40 12 2 45 45 1 1 45 30 1 1 Standard Methane 32 inch plume 40 12 2 45 45 1 1 45 30 1 1 Hi Arc Methane 32 inch plume 35 10 7 45 45 1 1 45 30 1 1 Very Hi Arc Fuel Size Distance feet m Horizontal degrees Typical Response Time seconds Vertical degrees Typ...

Страница 26: ...ch dia n Heptane 10 3 15 70 w sodium vapor lamp modulated unmodulated 3 0 9 1 x 1 foot n Heptane 40 12 0 1 250 w vapor lamp modulated unmodulated 3 0 9 1 x 1 foot n Heptane 40 12 0 1 300 w incandescent lamp modulated unmodulated 3 0 9 1 x 1 foot n Heptane 40 12 0 1 500 w halogen lamp modulated unmodulated 3 0 9 1 x 1 foot n Heptane 40 12 0 1 1500 w electric radiant heater modulated unmodulated 10 ...

Страница 27: ...Sensitivity Standard Mode FM Approval and Performance Report Continued Fuel Size Distance feet m Horizontal degrees Typical Response Time seconds Vertical degrees Typical Response seconds Black Powder 40 grams 5 1 5 45 45 0 1 0 1 45 30 0 1 0 1 ...

Страница 28: ...s Class I Division 1 Groups B C and D T5 Class II Division 1 Groups E F and G T5 Class I Division 2 Groups A B C and D T3 Class II Division 2 Groups F and G T3 Class III Enclosure Type 4X Ultraviolet Flame Detector Controller X2200 series rated 18 30 Vdc 2 5 Watts to 7 6 Watts Relay contacts rated 5 Amps 30 Vdc ...

Страница 29: ... use with the terminal compartment in type of explosion protection flameproof enclosure d or in type of explosion protection increased safety e for use with the terminal compartment in type of explosion protection increased safety e They shall be IP66 rated suitable for the conditions of use and correctly installed Unused entries shall be closed with suitable certified blanking elements The metal ...

Страница 30: ...ype of explosion protection flameproof enclosure d or in type of explosion protection increased safety e for use with the terminal compartment in type of explosion protection increased safety e They shall be IP66 rated suitable for the conditions of use and correctly installed Unused entries shall be closed with suitable certified blanking elements The metal housing for the Ultraviolet UV flame de...

Страница 31: ... OF THE APPROVAL UV Flame Detector Type X2200 for use in Automatic Fire Detection and Fire Alarm Systems BASIS OF APPROVAL DIN EN 54 Part 10 05 02 Flame Detectors INSTRUCTIONS FOR THE APPLICATION OF THE APPROVAL COMPONENT SYSTEM The Installation shall take into account that the orientation arrow on the flame detector is directed upwards as the view angle in this direction is 90 The UV flame detect...

Страница 32: ...ty oi are registered trademarks or trademarks of Detector Electronics Corporation in the United States other countries or both Other company product or service names may be trademarks or service marks of others Copyright Detector Electronics Corporation 2010 All rights reserved 95 8549 X3301 Multispectrum IR Flame Detector PointWatch Eclipse IR Combustible Gas Detector Eagle Quantum Premier Safety...

Отзывы: