24
95-8549
8.3
X2200M RESPONSE CHARACTERISTICS
High Sensitivity
X2200M FALSE ALARM IMMUNITY
High Sensitivity (Standard Mode)
FM Approval and Performance Report – Continued
MODEL X2200M
The X2200M uses a sensor that has a broader spectrum than the standard sensor. It is designed to detect fires with
unusual chemistry such as black powder. Consult factory for usage recommendations.
X2200M RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARMS
High Sensitivity (Standard Mode)
Fuel
Size
Distance
feet (m)
Typical Response Time
(seconds)
Mode
Black Powder
40 grams
10 (3)
0.1
Standard
False Alarm Source
Distance
feet (m)
Fire Source
Distance
feet (m)
Typical
Response Time
(seconds)
Sunlight, direct, reflected, modulated & unmodulated
—
2-inch dia n-Heptane
10 (3)
<15
70 w sodium vapor lamp, modulated & unmodulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
0.1
250 w vapor lamp, modulated & unmodulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
0.1
300 w incandescent lamp, modulated & unmodulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
0.1
500 w halogen lamp, modulated & unmodulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
0.1
1500 w electric radiant heater, modulated & unmodulated
10 (3)
1 x 1 foot n-Heptane
40 (12)
0.1
2-34 w fluorescent lamps, modulated & unmodulated
3 (0.9)
1 x 1 foot n-Heptane
40 (12)
0.1
False Alarm Source
Distance
feet (m)
Modulated Response
Unmodulated Response
Sunlight, direct, reflected
—
No Alarm
No Alarm
70 w sodium vapor lamp
3 (0.9)
No Alarm
No Alarm
250 w vapor lamp
3 (0.9)
No Alarm
No Alarm
300 w incandescent lamp
3 (0.9)
No Alarm
No Alarm
500 w halogen lamp
3 (0.9)
No Alarm
No Alarm
1500 w electric radiant heater
3 (0.9)
No Alarm
No Alarm
2-34 w fluorescent lamps
3 (0.9)
No Alarm
No Alarm