DO NOT TAMPER WITH WIRES WHEN POWER IS ON!

For alarms that are used as single non-interconnected, stand-alone alarms, do not connect the
yellow wire to anything. Insulate this wire (tape it) in place to make certain the yellow wire cannot
contact any metal parts.

Interconnected alarms can provide earlier warning of fire than stand-alone alarms, especially if a
fire starts in a remote area of the dwelling. When alarms are interconnected, all alarms will sound
when one alarm first goes into alarm. This alarm may be interconnected with a total of not more
than 24 interconnected devices, i.e., as many as 11 other USI ELECTRIC or UNIVERSAL model
smoke alarms or combination smoke and carbon monoxide (CO) or smoke and carbon monoxide
/ natural gas alarms; 6 other initiating alarms which may be a combination of USI ELECTRIC or
UNIVERSAL CO Alarms and Heat Alarms; and six other non-initiating devices such as USI
ELECTRIC Relay Modules.

This alarm can be interconnected with the following models:  

2995

5304

MI100, MI106

MDS211

,

MDS201,

 

2985,

 

5303

MI200, MI210

MDS101, MDS107, 3885

3895, MP118, MP117

3303

,

3304

MP202,

 

MP212

MDSCN111, MDSCN103, MICN109, MICN102, MCN105, MCN108, SS-

785, SS-790, SS-795, SS-2795, SS-2790, SS-2785, SS-2895, HD-130, USI-1103

USI-1203,

USI-1204, USI-1208 (Part #USI-1209

), 

USI-1213, USI-2430, USI-3204,

 

USI-5204, USI-5208,

USI-5213, USI-7385, USI-7390, USI-7485, USI-7490, CD-9385, CD-9390, CD-9485, CD-9490,
CD-9795, USI-7795 AND USI-960, RM-100 Relay.

When any one of these interconnected models goes into alarm, it will trigger the
corresponding alarm within the interconnected system with respect to their sensing
capabilities. Natural gas detection is only present in models MDSCN111, MSDCN103,
MICN109, MICN102, MCN108 and MCN105; therefore, a natural gas alarm will NOT trigger
the alarm of non-natural gas sensing models within an interconnected system.

The following alarms cannot reset units on an interconnected system: USI-7795, CD-9795,
USI-7385, USI-7390, USI-7485, USI-7490, CD-9385, CD-9390, CD-9485, CD-9490.

The following alarms cannot trigger QUICK FIND

®

 

 Alarm Origination on an interconnected

system: USI-7385, USI-7390, USI-7485, USI-7490, CD-9385, CD-9390, CD-9485, CD-9490.

The following alarms can trigger QUICK FIND

®

 

 Alarm Origination, but will not indicate

Alarm Origination on an interconnected system: USI-1103

USI-1203, USI-1204, USI-1208

(Part #USI-1209

), 

USI-1213, USI-5204, USI-5208, USI-5213, USI-3204, CD-9795, USI-7795,

USI-2430, SS-785, SS-790, SS-795, SS-2795, SS-2790, SS-2785, SS-2895, HD-130.

TO DEACTIVATE THE LOCKING FEATURES:

 To remove the alarm for cleaning or servicing or to

replace the battery, you must first remove the appropriate locking pin, if it has been installed.

1.

Turn off AC power to the circuit.

2.

Use long nose pliers to pull the locking pin out of the hole.

3.

It is now possible to remove the alarm or replace the battery.

WIRING INSTRUCTIONS:

1.

a.

The appropriate power supply is 120 Volt single phase power supplied from a non-switchable
circuit NOT protected by a ground fault circuit interrupter.

b.

Turn off AC power to the circuit before wiring the alarm.

c.

There are three pigtail wires (black, white and yellow) coming from the AC QUICK
CONNECTOR. The proper wire connection is as follows:

WIRES FROM QUICK CONNECTORCONNECT TO

BLACK

"HOT" side of AC line

WHITE

"NEUTRAL" side of AC line

YELLOW

Interconnect wires of other alarms

Page 8

2.

Insert the pin into the hole for the feature you are activating. Refer to the diagram below for
correct placement.

INSERT ALARM

LOCKING PIN HERE

INSERT BATTERY

LOCKING PIN HERE

Содержание MDSCN103 IoPhic

Страница 1: ...otect you and your family PLEASE READ AND SAVE Table of Contents Page Alarm Limitations and Functions 2 What You Should Know About CO 3 What You Should Know About Natural Gas 3 Basic Safety Informatio...

Страница 2: ...ETY HAZARDS LIKE SMOKING IN BED VIOLENT EXPLOSIONS ESCAPING GAS IMPROPER STORAGE OF FLAMMABLE MATERIALS OVERLOADED ELECTRICAL CIRCUITS CHILDREN PLAYING WITH MATCHES NATURAL CAUSES SUCH AS LIGHTNING OR...

Страница 3: ...ES This product is intended for use in ordinary indoor locations of family living units It is not designed to measure compliance with Occupational Safety and HealthAdministration OSHA commercial or in...

Страница 4: ...one sleeping area exists locate additional combination alarms in each sleeping area If a hall is more than 40 feet 12 meters long install a combination alarm at each end Locate additional alarms to p...

Страница 5: ...ay harm your hearing Make sure the alarm is not receiving excessively noisy power Examples of noisy power could be major appliances on the same circuit power from a generator or solar power light dimm...

Страница 6: ...et 6m from the sources or combustion particles stove furnace water heater space heater if possible In areas where a 20 foot 6m distance is not possible in modular mobile or smaller homes for example i...

Страница 7: ...ailure to connect this alarm to a 24 hour circuit may prevent it from providing constant protection IMPORTANT Do not subject this alarm to megger high voltage or high pot tests Remove the alarm s befo...

Страница 8: ...models MDSCN111 MSDCN103 MICN109 MICN102 MCN108 and MCN105 therefore a natural gas alarm will NOT trigger the alarm of non natural gas sensing models within an interconnected system The following alar...

Страница 9: ...time depends on the strength freshness of the battery The battery backup will not work unless a good battery is properly installed When the alarm utilizes battery backup power the natural gas sensor w...

Страница 10: ...Periodically the alarm measurement circuit is tested If an error is detected the alarm will sound 3 chirps approx every 20 seconds Reset the alarm If the unit does not reset replace the alarm END OF...

Страница 11: ...dangerous situation and the horn will sound again Ventilate area Page 11 Some individuals are more sensitive to CO than others including people with cardiac or respiratory problems infants unborn bab...

Страница 12: ...check for the presence of CO or gas WARNING Natural gas methane is highly explosive An attempt to test the unit by exposing it to natural gas outside of a controlled labatory environment can produce...

Страница 13: ...nt in other areas without reaching the alarm CO or gas could be present on one level of the home and not reach the alarm installed on a different level For example CO or gas in the basement may not re...

Страница 14: ...nsumer is exempt from any licensing or requirements Simultaneous operation of several fuel burning appliances competing for limited internal air Vent pipe connections vibrating loose from clothes drye...

Страница 15: ...sleeping area within 6 4 m 21 ft of any door to a sleeping room the distance measured along a path of travel 3 On every level of a dwelling unit including basements 4 On every level of a residential...

Страница 16: ...tedGASalarmhassensed GAS causing all interconnected units to sound If hazard is identified take all precautions if an alarm sounds by calling an Emergency Service and getting out of the home 3 Beeps 2...

Страница 17: ...2 Chirps approx every 20 seconds Off Off Condition Product End of Service Life Notification Recommendation Replace the alarm immediately The product end of service life notification can be temporaril...