Installation
03/19
Fl Protect Set
13
6.3
Installation of the Shut-off valve
The installation position of the shut-off valve (2) is not arbitrary!
It may be installed rotated around its own axis by max. +/- 90
degrees (armature tube and solenoid coil may point to the side,
but not downwards)! The valve must also be installed in the
correct direction (observe the flow direction arrow on the valve).
The valve body must be easy to open for maintenance work. The
Allen screws on the valve upper body must be accessible from
the outside.
The selected mounting position must allow the assembly and
disassembly of the control electronics (3) with solenoid coil (15).
The shut-off valve may only be screwed into the pipeline at the
flange connections using a fork wrench.
Install the shut-off valve (2) first!
Please observe the cable lengths and the visibility of the
front side of the Fl Protect when installing the
valve.
The upper part of the system (Fl Protect [3]) and
the plug connections must not be subjected to mechanical
stress (danger of destruction)!