Troubleshooting, Maintenance
03/19
Fl Set XL
32
9.2.2
Status display permanent yellow
Yellow (Duration)
Minor permanent water withdrawal or a small leak was
detected over a long period of time.
Water withdrawal or leakage was detected during
system restart.
Fl accurately indicates a pressure drop in the installation.
A few drops per minute can be detected as an error.
In most cases, the cause is leaking, dripping water outlets.
Examination:
Were any small quantities of water removed over a longer period
of time with short interruptions?
Were there people present?
Are there several slow dripping taps?
Do the solenoid valves of dishwashers and washing machines
really close tight?
Can drops be found on the taps?
Carefully check all water outlets.
Look for traces of limescale, e.g. in the toilet.
There were no persons present. Dripping end users are not
detectable:
Micro leaks in the piping system are possible!
Test the pipeline system for leaks (see chapter 8.1.4 "Test
operation").
If the fault persists and no cause can be found, a specialist is
required.