Getting Started
03/19
Fl Set XL
21
7.2
Sensitivity check
After installation and at regular intervals, the system should
be tested for correct functioning!
Allow a water tap to drip
Keep the Set / Reset button (8) pressed (max. 10 sec.) until the
status indicator flashes green/yellow and the Check indicator
flashes yellow. The system is now in test mode (see also chapter
8.1.4).
Observe whether the status display shows the green/yellow
Flashing (after max. 5 minutes) then permanently yellow.
WARNING
If the status display shows green (despite water
withdrawal), there is a fault!
Make sure that all lines are vented!
If no error can be detected and another test does not
indicate water withdrawal, a specialist must inspect your
installation.
The system is then not ready for operation until
clarification!
Switch the system to bypass operation (see section 8.1.3
"Bypass operation").