PORTABLE LPV TREATER
8. (Continued).
STEP 2: Start Generator.
Press the green Start
button on the generator. There will be a short pause
for system checks, then generator will begin cranking
over to start. Once the generator is running,
the display will show the voltage ramping up from
0 to 120 volts and an hour glass will appear in the
lower right corner of the screen untill both voltages
read 120v.
When L1N and L2N have reached 120v the hour glass
will turn into a motor piston moving up and down.
The generator is ready for use. Move the main power
disconnect switch to the right into the ON position.
Power is now available to the control panels,
spider box and hydraulic motor power switch.
If the generator fails to start after cranking for ten seconds,
it will pause for ten seconds and then begin cranking
a second time. If it fails to start after three attempts it will
stop and display an error message. Example: Low Fuel Level
or Battery Under Voltage. Once the problem is resolved,
press the Start button again.
NOTICE
GENERATOR OPERATION
STEP 3: Shutdown Generator.
When you are done treating, turn off the treater
panel, main control panel, pump stand mix motors and hydraulic motor. Move the
main disconnect switch to the left placing it in the OFF position. Shutdown the
generator by pressing the red Stop button. The hour glass will come back and after
the preset time elapses it will gradually reduce speed until it shutsdown. After it has
stopped running, move the control panel power switch down to the OFF position.
If left on it will drain the generator battery.
For an operators manual with more detailed information regarding the display functions
go to the Deep Sea Electronics website and download document number 057-260 at:
https://www.deepseaplc.com/genset/manual-auto-start-control-modules/dse4510