12.3 Analogue thermostat T-163, alarms/problems
An alarm is sent when more than 1 hour have elapsed since the controller received the last radio signal from the thermostat.
The table below lists problems that can occur in the public thermostat T-163.
Indication
Probable cause
Solutions
The LED flashes twice
The thermostat battery power is running low
Replace the batteries
12.4 Controller, alarms/problems
An alarm is sent when more than 1 hour have elapsed since the controller received the last radio signal from the thermostat.
The table below lists problems that can occur in the controller.
Indication
Probable cause
Solutions
The radio icon
is not displayed in
the controller display
The antenna is out of position or the wire is
disconnected
Install the antenna in a correct position with the wire
correctly connected
12.5 Contact installer
For installer contact information, see the installation
report in the end of this document. Prepare the
following information before contacting an installer:
• Installation report
• Drawings of the underfloor heating system (if
available)
• List of all alarms, including time and date
12.6 Installer instructions
To determine if a problem is caused by the supply
system or the control system, loosen the actuators
from the manifold for the room concerned. Wait a few
minutes and check if the flow pipe of the underfloor
heating loop becomes warm.
If the pipe does not become warm, the problem is in the
heating system. If the loop becomes warm, the cause
could be the room control system.
A supply system defect can be indicated by no warm
water in the manifold. Check the boiler and circulation
pump.