8.6 System parameter settings
In this menu, settings regarding the operation of the
controller is set.
N OT E !
Some system parameter settings are only
accessible during the first 4 hours after
power up. This is done to prevent mistakes
after installation. If the locked system
parameter symbol is displayed, the power
to the controller has to be disconnected
and reconnected again to modify these
parameters. No settings are lost when
disconnecting, or after a power failure.
The settings available while in run mode is
always accessible for change, and will not be
locked.
N OT E !
If no button on the controller is pressed for
about 4 minutes, the software exits to run
mode.
To enter system parameter settings:
1. Press and hold the
OK
button for about 10 seconds.
2. The settings icon is displayed in the top left hand
corner of the display, and the text
Hot type
,
Cld
type
, or
rEv type
(depending of current operating
mode) is displayed.
3. Use buttons
<
or
>
to locate a parameter (see list
below) and press
OK
.
Some of these parameters require other parameters
to activate them.
4. Use buttons
-
or
+
to change parameter settings.
Menu Display
Description
0
type
Type of installation (heating and/
or cooling)
1
Cur
Heating curve
2
Hi
Maximum supply temperature
(heating mode)
3
Lo
Minimum supply temperature
(heating mode)
1
Cur
Cooling curve
2
Hi
Maximum supply temperature
(cooling mode)
3
Lo
Minimum supply temperature
(cooling mode)
4
InSt
Type of system (hydraulic
installation)
5
th
Thermostat selection (installed/
wireless/etc)
6
tHty
Wired thermostat configuration
(Not used by Move/Move PLUS)
Menu Display
Description
7
BGAP
Boost function, if the difference
between the supply and return
temperature is too high
8
trF1
Wireless thermostat 1 configuration
9
trF2
Wireless thermostat 2 configuration
10
tr1o
Supply temperature compensation,
when using a thermostat to speed
up the system. Use with caution
11
in1
Wired input 1, select function
12
in2
Wired input 2, select function
13
OUSE
Outdoor sensor selection
(installed/wireless/wired/etc)
14
OUt
Outdoor temperature, fixed value if
outdoor sensor is not installed
15
ourF
Wireless outdoor sensor
configuration
16
˚C
Display unit
17
00:00
Time unit (AM/PM/24H)
18
GriP
Valve and pump exercise
19
PUMP
Pump delay, start delay after the
mixer valve is closed
20
ctrl
Forced control, of the actuator
21
PrH
Floor/screed preheating program
22
dry
Floor/screed drying program
23
ALL
Factory reset
24
End
Exit system parameter settings
5. Use buttons
<
or
>
to locate parameter
24 (End)
– Exit system parameter settings.
6. Press the
OK
button to exit the system parameter
settings.
0 – Type of installation
0h
Select whether the installation is a heating and/or
cooling system.
N OT E !
When registering a thermostat to the
controller (Move PLUS only), run mode
changes parameter
0 (type)
to
rEv
,
regardless of previous setting. Heating/
cooling is then controlled by the thermostat,
or the integrated system.