Single-stage SetPoint Controller Installation & Operation Manual
Choose the placement of the thermostats early in the construction process to enable proper
wiring during rough-in.
Consider the following:
• Install on an interior wall.
• Keep dry. Avoid potential leakage onto the control.
• Ensure relative humidity is less than 90% (non-condensing environment).
• Do not expose to extreme temperatures beyond 32-122°F (0-50°C).
• Do not expose to draft, direct sun, or other cause for inaccurate
temperature readings.
• Install away from equipment, appliances, or other sources of electrical interference.
• Ensure easy access for wiring, viewing, and adjusting the display screen.
• Install approximately 5 feet (1.5m) off the finished floor.
• The maximum length of wire is 500 feet (150m).
• Strip wire to
3
⁄
8
" (10mm) for all terminal connections.
• Use standard, 4-conductor, 18-AWG wire.
Installation Location
----------------------------------------
Materials Required
-----------------------------------------
• 18 AWG LVT Solid Wire
(Low-voltage Connections)
Removing the Thermostat Base
To remove the thermostat base:
• Locate the tab on the bottom of the thermostat.
• Push the tab with either your thumb or with a
screwdriver.
• Lift the thermostat front away from the
thermostat’s base.