Single-stage SetPoint Controller Installation & Operation Manual
Programmable Settings
Setting
Display
User settings. Press the
and
buttons together for 3 seconds to enter and
advance to the next setting.
MODE
Select heat or off.
Range: HEAT, OFF
Default: HEAT
UNITS
Select the temperature units.
Range: °F or °C
Default: °F
LIGHT
Select when the display backlight should operate. Auto operates
the backlight for 30 seconds after a keystroke.
Range: OFF, AUTO, ON
Default: AUTO
SET FLOOR
Set the floor minimum temperature. Available when an auxiliary
floor sensor is connected and the built-in room sensor is on.
F
Range: OFF, 40 to 122°F (4.5 to 50.0°C)
Default: 72°F (22.0°C)
TYPE
Device Type number. Hold the button to view the
software version.
ESCAPE
Release the and buttons to return to the home screen.
Installer settings. Press the
and
buttons together for 5 more seconds.
AUXILIARY SENSOR
Select the type of auxiliary sensor. Available when an auxiliary sensor
is automatically detected.
Range:
NONE
= no auxiliary sensor,
ROOM
= Indoor Sensor,
FLOR
= Floor Sensor,
OUT
= Outdoor Sensor
Default: OFF
ROOM SENSOR
Select if the built-in room temperature sensor is on or off. The
built-in room sensor can only be disabled when an auxiliary room
or floor sensor is connected.
Room
Range: ON or OFF
Default: ON
SET FLOOR MAXIMUM
Set the floor maximum temperature in order to protect the floor
covering. Suggested settings: Tile = 90°F (32°C), Wood Floor =
85°F (29°C)
F
MAX
Range: 40 to 122°F (4.5 to 50.0°C), OFF
Default: 85°F (29.5°C)
ESCAPE
Release the and buttons to return to the home screen.