20
LTE Primary Cellular
Alarm Communicator
LTE30EX
(INSTALLATION continued next page)
INSTALLATION (cont.)
Input 1 if Standard Type
FIGURE 3: Wiring example for voltage trip
Voltage Trip -
Input 1 if set for standard input can be tripped by applying 12 V to the +
input and 0 V to the - input. A signal must be continuously present for 500 ms.
FIGURE 4: Wiring example for open collector trip
Open Collector -
Inputs 1 if set for standard input can be tripped by applying 12 V to the
+ input and the Open Collector output of the panel to the - input. A signal must be
continuously present for 500 ms.