27
LTE Primary Cellular
Alarm Communicator
LTE30EX
APPENDIX A:
CONTACT ID, SIA EVENT, AND
MODEM II
e
/III
a
2
CODES
Following is a list of event codes that can be sent to the central station receiver for
events generated by the LTE30EX:
EVENT DESCRIPTION
CONTACT ID
EVENT CODE
SIA DC-03
EVENT CODE
MODEM IIe/llla
2
AC Fail
E301
AT
48
AC Restoral
R301
AR
49
Alarm (generic)
E140
UA
10
Burglary Alarm
E130
BA
10
Burglary Restoral
R130
BR
12
Burglary Tamper
E137
TA
10
Burglary Tamper Restoral
R137
TR
12
Closing
R400
CL
32
Fire Alarm
E110
FA
0B
Fire Restoral
R110
FR
0E
Fire Supervisory
E200
FS
11
Fire Supervisory Restoral
R200
FJ
12
High Temperature
E158
KA
10
High Temperature Restoral
R158
KR
12
Holdup Alarm
E122
HA
10
Holdup Restoral
R122
HR
12
Low Battery
E302
YT
4B
Low Battery Restoral
R302
YR
4C
Low Temperature
E159
ZA
10