![Uplink LTE30EX Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/uplink/lte30ex/lte30ex_installation-and-user-manual_1060811006.webp)
5
LTE Primary Cellular
Alarm Communicator
LTE30EX
KEY FEATURES
A. FULL DATA Reporting.
Compatible with most alarm panels using Contact ID (SIA
DC-05 Standard), SIA FSK Level 1 (SIA DC-03 Standard), Modem IIe/IIIa
2
or Pulse
4/2 digital dialer formats. All information sent by the alarm panel in these formats
(account number, zone information, User IDs, etc.) will be sent to the central
station using the LTE network or HSPA 3G network when LTE is not available.
B. Power Requirements:
Requires constant 12V DC power from a power supply,
battery, or alarm panel with a constant 125mA and a peak 600 mA for one second
during transmission.
C. Panel to LTE30EX Cable Supervision.
Monitors continuity of the cable connecting
the panel’s telephone dialer to the LTE30EX. This feature is activated through the
website
www.uplink.com
or by calling Uplink Technical Support:
1-888-9-UPLINK
(1-888-987-5465)
D. Input.
The LTE30EX has one programmable input. This input can be programmed
to one of the following functions via the website:
• Standard Input
• Sampled Siren
• Pulse Counter
• Timed Bell
E. Output.
The LTE30EX has one programmable relay output. This output can be
programmed to activate upon the occurrence of one or more of the following
trouble conditions:
• Cellular Network Loss
• No Central Station Acknowledgement
• Low DC input Voltage
• Panel/4530EX Cable Supervision Trouble
• Unit Disabled by Dealer Command
• Watchdog Circuit Activation
F. Power Source Monitoring (Low DC Input Voltage Reporting).
The LTE30EX can report a
low input Voltage condition to the central station when its DC input voltage drops
below 10.2V DC. It will report Low input Voltage Restoral at 11.4V DC.