Electric Combination Boiler User Manual
The protective grounding line must be connected to the exposed metal parts of the other devices in the
installation location and to the local and national requirements for the grounding line to which the device is
installed. To obtain maximum efficiency from the device, the shortest cable distance between the fuse board
and the device must be used. Cable length is also important in terms of circuit break time and temperature limits.
There is a maximum permissible cable length limitation in a line combination to be created for the current
requirement, voltage drop and cable cross-section. If the cables are surrounded by thermal insulation, installed
inside the wall, passed through a place with a temperature higher than 30 ° C or tied together, the amount of
current passing through the cable is reduced. To achieve the same current values, a larger cable cross-section
must be
selected.
ELECTRIC INSTALLATION INSTRUCTIONS
THIS PRODUCT MUST BE EARTHED!
The boiler must be closed and should not be installed in living spaces.