Goodrive10 inverters Function codes
55
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P08.33
FDT retention
detection
value
detect FDT” until the output frequency decreases to a value
lower than (FDT electrical level
—
FDT retention detection
value) the corresponding frequency, the signal is invalid.
Below is the waveform diagram:
Setting range of P08.32: 0.00Hz~P00.03(the Max.
frequency)
Setting range of P08.33: 0.0~100.0%(FDT electrical level)
5.0%
○
P08.36
Frequency
arrival
detection
value
When the output frequency is among the below or above
range of the set frequency, the multi-function digital output
terminal will output the signal of “frequency arrival”, see the
diagram below for detailed information:
The setting range: 0.00Hz~P00.03(the Max. frequency)
0.00Hz
○
P08.37
Energy
Braking enable
This parameter is used to control the internal braking pipe.
0: Disabled
1: Enabled
Note: Only applied to internal braking pipe.
0
○
P08.38
Energy
Braking
threshold
voltage
After setting the original bus voltage to brake the energy,
adjust the voltage appropriately to brake the load. The
factory changes with the voltage level.
The setting range:200.0~2000.0V
In order to prevent customers set the value is too large, it is
recommended setting range:
220V
voltage:
380.0V
○
380V
voltage:
700.0V