Goodrive10 inverters Function codes
27
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
running state to make the inverter coast to stop.
1:Terminal running co
mmand channel (“
LOCAL/REMOT
”
flickering)
Carry out the running command control by the forward
rotation, reverse rotation and forward jogging and reverse
jogging of the multi-function terminals
2:Communication running command channel
(“
LOCAL/REMOT
” on)
;
The running command is controlled by the upper monitor
via communication
P00.03
Max. output
frequency
This parameter is used to set the maximum output
frequency of the inverter. Users should pay attention to this
parameter because it is the foundation of the frequency
setting and the speed of acceleration and deceleration.
Setting range: P00.04~400.00Hz
50.00Hz
◎
P00.04
Upper limit of
the running
frequency
The upper limit of the running frequency is the upper limit of
the output frequency of the inverter which is lower than or
equal to the maximum frequency.
Setting range:P00.05~P00.03 (Max. output frequency)
50.00Hz
◎
P00.05
Lower limit of
the running
frequency
The lower limit of the running frequency is that of the output
frequency of the inverter.
The inverter runs at the lower limit frequency if the set
frequency is lower than the lower limit one.
Note:
Max. output frequency ≥ Upper limit frequency ≥
Lower limit frequency
Setting range:0.00Hz~P00.04 (Upper limit of the running
frequency)
0.00Hz
◎
P00.06
A frequency
command
selection
Note:
Frequency A and frequency B cannot use the same
frequency setting mode. The frequency source can be set
by P00.09.
0:Keypad data setting
Modify the value of function code P00.10 (set the frequency
by keypad) to modify the frequency by the keypad.
1:Analog AI1 setting
2:Analog AI2 setting
0
○
P00.07
B frequency
command
selection
2
○