background image

V200-18-E2B   

S n a p - i n   I / O   M o d u l e

 10/06

 

10 

Unitronics 

 

 

Analog Outputs 

 

Number of outputs 

2 (single-ended) 

Output range 

0-10V, 0-20mA, 4-20mA.  See Note 5. 

Resolution (except at 4-20mA) 
Resolution at 4-20mA 

12-bit (4096 units)  
819 to 4095 (3277 units) 

Conversion time 

Synchronized to scan time. 

Load impedance 

1k

 minimum—voltage 

500

 maximum—current 

Galvanic isolation 

None 

Linearity error 

±0.1% 

Operational error limits 

±0.2% 

Notes: 

 

5. 

Note that the range of each I/O is defined both by wiring and within the controller’s software. 

Environmental 

IP20 / NEMA1 

Operating temperature 

0

°

 to 50

°

C (32

°

 to 122

°

F) 

Storage temperature 

-20

°

 to 60

°

 C (-4

°

 to 140

°

F) 

Relative Humidity (RH) 

5% to 95% (non-condensing) 

Dimensions 

 

Size (WxHxD) 

138x23x123mm (5.43x0.9x4.84”) 

Weight  

231g (8.13 oz) 

 
 
 
 
About Unitronics 

Unitronics has been producing PLCs, automation software and accessory devices since 1989.  
Unitronics’ OPLC controllers combine full-function PLCs and HMI operating panels into single, compact units.  
These HMI + PLC devices are programmed in a single, user-friendly environment.  Our clients save I/O points, 
wiring, space, and programming time; elements that translate directly into cost-efficiency. 
Unitronics supports a global network of distributors and sales representatives, as well as a U.S. subsidiary. 
For more information regarding Unitronics products, contact your distributor or Unitronics headquarters via 
email: 

[email protected]

 
 
 
 
 
 

The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and 
without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of 
the forgoing from the market. 
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of 
merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in 
this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or 
in connection with the use or performance of this information. 
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other third 
parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them 

5410-1042-7

 

 

Содержание V200-18-E2B

Страница 1: ...d with the device s electrical wiring Symbol Meaning Description Danger The identified danger causes physical and property damage Warning The identified danger can cause physical and property damage Symbols are used to highlight information relating to the user s personal safety and equipment protection throughout this document When these symbols appear the associated information must be read care...

Страница 2: ...the controller You must remove this cap before installing a module 1 Pry the cap off using the blade of a screwdriver 2 Line the circular guidelines on the controller up with the guidelines on the module as shown below 3 Apply even pressure on all 4 corners until you hear a distinct click The module is now installed Check that all sides and corners are correctly aligned Removing a Snap in I O Modu...

Страница 3: ...maximum torque of 0 5 N m 5 kgf m Do not use tin solder or any other substance on stripped wire that might cause the wire strand to break Install at maximum distance from high voltage cables and power equipment I O Wiring General Input or output cables should not be run through the same multi core cable or share the same wire Allow for voltage drop and noise interference with input lines used over...

Страница 4: ... npn sink digital input wiring pnp source digital input wiring npn sink high speed counter pnp source high speed counter Inputs I0 I1 and I2 I3 can be used as shaft encoders as shown below npn sink shaft encoder wiring pnp source shaft encoder wiring ...

Страница 5: ...mity to voltage power supply specifications connect the device to a regulated power supply Do not connect the Neutral or Line signal of the 110 220VAC to the device s 0V pin Relay Outputs The 0V signal of the relay outputs is isolated from the controller s 0V signal Increasing Contact Life Span To increase the life span of the relay output contacts and protect the device from potential damage by r...

Страница 6: ...gnal of the transistor outputs is isolated from the controller s 0V signal npn sink pnp source Analog Inputs Shields should be connected at the signal source Inputs may be wired to work with either current or voltage Note that the analog input s 0V signal must be the same 0V used by the controller s power supply current current voltage ...

Страница 7: ...d to the chassis Do not connect the Neutral or Line signal of the 110 220VAC to the device s 0V pin In the event of voltage fluctuations or non conformity to voltage power supply specifications connect the device to a regulated power supply The 24VDC power supply must be turned on and off simultaneously with the controller s power supply Output Wiring Shields should be earthed connected to the ear...

Страница 8: ...ital input normal input specifications apply 2 Inputs 1 and 3 can each function as either counter reset or as a normal digital input in either case its specifications are those of a normal digital input These inputs may also be used as part of a shaft encoder In this case high speed input specifications apply Relay Outputs Number of outputs 10 See Note 3 Output type SPST NO relay Form A Isolation ...

Страница 9: ...m See Note 4 Short circuit protection Yes pnp only Power supply operating voltage 20 4 to 28 8VDC nominal operating voltage 24VDC npn sink power supply operating voltage 3 5V to 28 8VDC unrelated to the voltage of either the I O module or the controller Notes 4 Outputs 12 and Output 13 may be used as high speed outputs Analog Inputs Number of inputs 2 single ended Input range 0 10V 0 20mA 4 20mA S...

Страница 10: ...entatives as well as a U S subsidiary For more information regarding Unitronics products contact your distributor or Unitronics headquarters via email export unitronics com The information in this document reflects products at the date of printing Unitronics reserves the right subject to all applicable laws at any time at its sole discretion and without notice to discontinue or change the features...

Отзывы: