HMI Panel Installation Guide  

 

 

Unitronics 

 

Panel Mounting 

 

 

N

OTE

 

 

Mounting panel thickness must be less or equal to 5mm (0.2”). 

 

Ensure that the space considerations are met. 

1.  Prepare a panel cut-out according to the dimensions of your model, USP-070-B10, 

USP-104-B10, USP-104-M10 or USP-156-B10 as shown in the previous section. 

2.  Slide the panel into the cut-out, 

ensuring that the Panel Mounting Seal is 

in place as shown on the right. 

3.  Push the mounting brackets into their 

slots on the sides of the panel as shown 

below. 

4.  Tighten the bracket screws against the 

panel. Hold the brackets securely 

against the unit while tightening the 

screws. 

When properly mounted, the panel is 

squarely situated in the panel cut-out as 

shown below. 

 

 

 

USP-070-B10: 4 mounting brackets 

USP-104-B10,

 

USP-104-M10 : 8 mounting 

brackets 

 

USP-156-B10: 10 mounting brackets 

 

  

Содержание UniStream USP-070-B10

Страница 1: ...acing Uni I O Uni COM modules Isolated RS485 and CANbus ports Backup battery HMI Panels Available in different dimensions A high resolution touch screen provides the operator interface for the system and the physical foundation for a PLC HMI I Os all in one controller The DIN rail structure on the panel s back is designed to physically support a CPU for Panel controller Uni I O and or Uni COM modu...

Страница 2: ...ct should be installed only by qualified personnel Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels Do not connect disconnect the device when power is on Environmental Considerations Ventilation 10mm 0 4 of space is required between the device top bottom edges and the enc...

Страница 3: ...liance 3 DIN rail structure Physical support for the CPU for Panel Uni I O and or Uni COM modules 4 12 24VDC power input Connection point for the HMI Panel s power source Connect the Terminal Block supplied with the kit to the end of the power cable 5 2 Ethernet RJ45 ports Support high speed Ethernet communications 6 USB Device Use for application download and direct PC UniStream communication 7 2...

Страница 4: ...nsiderations Allocate space for The HMI Panel including the CPU and any modules that will be installed on it Opening the doors of the CPU and modules For exact dimensions please refer to the Mechanical Dimensions shown below HMI Panel Mechanical Dimensions 7 Panel ...

Страница 5: ...UniStream Unitronics 5 10 4 Panel 15 6 Panel ...

Страница 6: ...ion 2 Slide the panel into the cut out ensuring that the Panel Mounting Seal is in place as shown on the right 3 Push the mounting brackets into their slots on the sides of the panel as shown below 4 Tighten the bracket screws against the panel Hold the brackets securely against the unit while tightening the screws When properly mounted the panel is squarely situated in the panel cut out as shown ...

Страница 7: ... from high voltage cables and power equipment Wiring Procedure Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm2 3 31 mm2 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure a proper connection 4 Tighten enough to keep the wire from pulling free Wiring Guid...

Страница 8: ...kets taking care to support the panel to prevent it from falling during this procedure The information in this documentreflects products at the date of printing Unitronics reserves the right subject to allapplicable laws at any time at itssole discretion and without notice to discontinue or change the features designs materialsand otherspecifications of its products and to either permanently or te...

Отзывы: