background image

UniStream™ 

 

Unitronics 

 

 

Wiring 

 

 

 

 

This equipment is designed to operate only at SELV/PELV/Class 2/Limited Power 

environments. 

 

All power supplies in the system must include double insulation. Power supply 

outputs must be rated as SELV/PELV/Class 2/Limited Power. 

 

Do not connect either the ‘Neutral’ or ‘Line’ signal of the 110/220VAC to device’s 0V 
point. 

 

Do not touch live wires. 

 

All wiring activities should be performed while power is OFF. 

 

Use over-current protection, such as a fuse or circuit breaker, to avoid excessive 
currents into the HMI Panel supply port.  

 

Unused points should not be connected (unless otherwise specified). Ignoring this 
directive may damage the device. 

 

Double-check all wiring before turning on the power supply. 

Caution 

 

To avoid damaging the wire, use a maximum torque of 0.5 N·m (5 kgf·cm). 

 

Do not use tin, solder, or any substance on stripped wire that might cause the 

wire strand to break. 

 

Install at maximum distance from high-voltage cables and power equipment. 

  

 

Wiring Procedure 

Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm

2

 –3.31 mm

2

). 

1.  Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).  
2.  Unscrew the terminal to its widest position before inserting a wire.  
3.  Insert the wire completely into the terminal to ensure a proper connection. 
4.  Tighten enough to keep the wire from pulling free. 

 

Wiring Guidelines 

In order to ensure that the device will operate properly and to avoid electromagnetic 

interference: 

 

Use a metal cabinet. Make sure the cabinet and its doors are properly earthed. 

 

Use wires that are properly sized for the load. 

 

Individually connect each 0V point in the system to the power supply 0V terminal. 

 

Individually connect each functional ground point ( ) to the earth of the system 
(preferably to the metal cabinet chassis). 

Use the shortest and thickest wires possible: less than 1m (3.3’) in length, minimum 

thickness 14 AWG (2 mm

2

). 

 

Connect the power supply 0V to the earth of the system. 

N

OTE

 

For detailed information, refer to the document System Wiring Guidelines, 

located in the Technical Library in the Unitronics’ website. 

 

 

 

Содержание UniStream USP-070-B10

Страница 1: ...acing Uni I O Uni COM modules Isolated RS485 and CANbus ports Backup battery HMI Panels Available in different dimensions A high resolution touch screen provides the operator interface for the system and the physical foundation for a PLC HMI I Os all in one controller The DIN rail structure on the panel s back is designed to physically support a CPU for Panel controller Uni I O and or Uni COM modu...

Страница 2: ...ct should be installed only by qualified personnel Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels Do not connect disconnect the device when power is on Environmental Considerations Ventilation 10mm 0 4 of space is required between the device top bottom edges and the enc...

Страница 3: ...liance 3 DIN rail structure Physical support for the CPU for Panel Uni I O and or Uni COM modules 4 12 24VDC power input Connection point for the HMI Panel s power source Connect the Terminal Block supplied with the kit to the end of the power cable 5 2 Ethernet RJ45 ports Support high speed Ethernet communications 6 USB Device Use for application download and direct PC UniStream communication 7 2...

Страница 4: ...nsiderations Allocate space for The HMI Panel including the CPU and any modules that will be installed on it Opening the doors of the CPU and modules For exact dimensions please refer to the Mechanical Dimensions shown below HMI Panel Mechanical Dimensions 7 Panel ...

Страница 5: ...UniStream Unitronics 5 10 4 Panel 15 6 Panel ...

Страница 6: ...ion 2 Slide the panel into the cut out ensuring that the Panel Mounting Seal is in place as shown on the right 3 Push the mounting brackets into their slots on the sides of the panel as shown below 4 Tighten the bracket screws against the panel Hold the brackets securely against the unit while tightening the screws When properly mounted the panel is squarely situated in the panel cut out as shown ...

Страница 7: ... from high voltage cables and power equipment Wiring Procedure Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm2 3 31 mm2 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure a proper connection 4 Tighten enough to keep the wire from pulling free Wiring Guid...

Страница 8: ...kets taking care to support the panel to prevent it from falling during this procedure The information in this documentreflects products at the date of printing Unitronics reserves the right subject to allapplicable laws at any time at itssole discretion and without notice to discontinue or change the features designs materialsand otherspecifications of its products and to either permanently or te...

Отзывы: