Engineering Guide
Space Saver
20
Subject to change without notice.
20.3-TD (1018)
Chilled Water Coil Performance
VSCW10G* Valve Size: 1"
EWT
GPM
PD Ft H20
CFM
86 / 72
80 / 67
75 / 62.5
72 / 60
Total
Sensible
Total
Sensible
Total
Sensible
Total
Sensible
48
27
19.7
4400
112,090
89,920
106,760
87,570
101,950
85,800
98,210
83,700
4000
110,330
87,310
105,080
85,020
100,350
83,310
96,670
81,270
3600
108,780
84,690
103,600
82,460
98,940
80,810
95,310
78,830
18
9
4400
100,620
80,730
95,830
78,600
91,520
77,030
88,160
75,140
4000
99,040
78,380
94,330
76,320
90,080
74,790
86,780
12,960
3600
97,650
76,020
93,000
74,030
88,810
72,540
85,560
70,770
9
2.37
4400
77,240
61,970
73,560
60,340
70,250
59,130
67,670
57,690
4000
76,030
60,170
72,410
58,590
69,150
57,410
66,610
56,010
3600
74,960
58,360
71,390
56,830
68,180
55,680
65,670
54,320
45
27
19.7
4400
124,560
99,920
118,630
97,290
113,290
95,340
109,130
93,000
4000
122,600
97,010
116,770
94,460
111,510
92,570
107,420
90,300
3600
120,880
94,090
115,130
91,620
109,940
89,790
105,910
87,590
18
9
4400
111,820
89,690
106,490
87,340
101,700
85,590
97,970
83,490
4000
110,060
87,080
104,820
84,800
100,100
83,100
96,430
81,060
3600
108,510
84,460
103,350
82,250
98,690
80,600
95,070
78,620
9
2.37
4400
85,840
68,850
81,750
67,050
78,060
65,700
75,210
64,090
4000
84,490
66,850
80,470
65,100
76,840
63,790
74,030
62,230
3600
83,300
64,840
79,340
63,140
75,760
61,870
72,990
60,360
42
27
19.7
4400
137,010
109,910
130,490
107,020
124,620
104,880
120,050
102,300
4000
134,860
106,710
128,440
103,910
122,660
101,830
118,160
99,330
3600
132,970
103,500
126,640
100,790
120,940
98,770
116,500
96,350
18
9
4400
122,990
98,660
117,140
96,070
111,870
94,150
107,760
91,840
4000
121,060
95,790
115,300
93,280
110,110
91,410
106,070
89,170
3600
119,360
92,910
113,680
90,480
108,560
88,660
104,580
86,490
9
2.37
4400
94,410
75,740
89,920
73,750
85,870
72,270
82,720
70,500
4000
92,930
73,540
88,510
71,610
84,520
10,170
81,420
68,450
3600
91,620
71,330
87,270
69,460
83,330
68,060
80,280
66,390
Notes:
(1) Performance based on water as the chilled fluid.
(2) Pressure drop is for the coil only and does not Include a valve�
(3) Unit shipped with coil stubbed through the cabinet and capped�
(4) Pressure drops over 10 Ft. H20 are considered excessive.
Contact the factory for a special coil selection to meet your specific parameters.