Engineering Guide
Space Saver
18
Subject to change without notice.
20.3-TD (0917)
Chilled Water Coil Performance
VSCW7G* Valve Size: 1"
EWT
GPM
PD Ft H20
CFM
86 / 72
80 / 67
75 / 62.5
72 / 60
Total
Sensible
Total
Sensible
Total
Sensible
Total
Sensible
48
18
15.35
3080
79,060
61,660
75,300
60,040
71,910
58,840
69,280
57,400
2800
77,820
59,870
74,120
58,300
70,780
57,130
68,190
55,730
2520
76,730
58,070
73,080
56,550
69,780
55,410
67,230
54,050
12
7
3080
70,970
55,360
67,600
53,910
64,550
52,820
62,180
51,530
2800
69,860
53,750
66,540
52,340
63,540
51,290
61,210
50,030
2520
68,880
52,130
65,600
50,760
62,650
49,750
60,350
48,520
6
1.84
3080
54,480
42,490
51,890
41,380
49,560
40,550
47,740
39,560
2800
53,630
41,260
51,080
40,180
48,780
39,370
46,990
38,410
2520
52,870
40,020
50,360
38,970
48,090
38,180
46,330
37,250
45
18
15.35
3080
87,860
68,520
83,680
66,730
79,910
65,390
76,990
63,780
2800
86,480
66,530
82,370
64,790
78,660
63,490
15,780
61,930
2520
85,260
64,530
81,210
62,840
77,550
61,580
74,710
60,070
12
7
3080
78,870
61,520
75,120
59,900
71,730
58,690
69,100
57,260
2800
77,630
59,730
73,940
58,160
70,610
56,990
68,020
55,600
2520
76,540
57,930
72,900
56,410
69,620
55,280
67,060
53,930
6
1.84
3080
60,540
47,220
57,660
45,980
55,060
45,060
53,040
43,960
2800
59,590
45,850
56,760
44,650
54,200
43,750
52,210
42,680
2520
58,750
44,470
55,960
43,310
53,440
42,430
51,470
41,390
42
18
15.35
3080
96,650
75,370
92,040
73,390
87:900
71,920
84,680
70,160
2800
95,130
73,180
90,600
71,260
86,520
69,830
83,350
68,120
2520
93,790
70,980
89,330
69,120
85,300
67,730
82,180
66,070
12
7
3080
86,750
67,660
82,630
65,880
78,910
64,570
76,010
62,980
2800
85,390
65,690
81,330
63,970
77,670
62,690
74,820
61,150
2520
84,190
63,710
80,190
62,050
76,580
60,800
73,770
59,310
6
1.84
3080
66,590
51,940
63,420
50,580
60,570
49,560
58,340
48,340
2800
65,550
50,430
62,430
49,110
59,620
48,120
57,430
46,940
2520
64,630
48,910
61,550
47,630
58,780
46,670
56,620
45,530
Notes:
(1) Performance based on water as the chilled fluid.
(2) Pressure drop is for the coil only and does not Include a valve�
(3) Unit shipped with coil stubbed through the cabinet and capped�
(4) Pressure drops over 10 Ft. H20 are considered excessive.
Contact the factory for a special coil selection to meet your specific parameters.