Engineering Guide
Space Saver
13
Subject to change without notice.
20.3-TD (1018)
Chilled Water Coil Performance
VSCW2G* Valve Size: 1/2"
EWT
GPM
PD Ft H20
CFM
86 / 72
80 / 67
75 / 62.5
72 / 60
Total
Sensible
Total
Sensible
Total
Sensible
Total
Sensible
48
5.25
15.35
880
18,170
14,920
17,310
14,530
16,530
14,230
15,920
13,880
800
17,890
14,490
17,040
14,110
16,270
13,820
15,670
13,480
720
17,630
14,050
16,800
13,680
16,040
13.400
15,450
13,070
3.5
7
880
16,310
13.400
15,540
13,050
14,840
12,780
14,290
12.4,0
800
16,060
13,010
15,300
12,670
14,610
12,410
14,070
12,110
720
15,830
12,610
15,080
12,280
14.400
12,030
13,870
11,740
1.75
1.84
880
12,510
10,270
11,920
10,010
11,380
9,800
10,970
9,560
800
12,320
9,980
11,740
9,720
11,210
9,520
10,800
9,290
720
12,140
9,680
11,570
9,420
11,050
9,230
10,640
9,010
45
5.25
15.35
880
20,180
16,580
19,230
16,150
18,350
15,820
17,680
15,430
800
19,870
16,100
18,930
15,680
18,070
15,360
17,410
14,990
720
19,590
15,610
18,660
15,200
17,810
14,890
17,160
14,540
3.5
7
880
18,130
14,890
17,270
14,500
16,480
14,200
15,890
13,860
800
17,850
14,460
17,000
14,080
16,230
13,790
15,640
13,460
720
17,600
14,020
16,760
13,650
16,000
13,370
15,420
13,050
1.75
1.84
880
13,910
11,420
13,250
11,120
12,650
10,890
12,190
10,620
800
13,700
11,090
13,050
10,800
12,460
10,580
12,000
10,320
720
13,500
10,750
12,860
10,470
12,280
10,260
11,830
10,010
42
5.25
15.35
880
22,210
18,230
21,160
17,750
20,200
17,390
19,460
16,970
800
21,870
17,700
20,830
17,240
19,890
16,890
19,160
16,480
720
21,560
17,160
20,530
16,720
19,610
16,380
18,890
15,980
3.5
7
880
19,940
16,360
18,990
15,940
18,130
15,620
17,470
15,230
800
19,630
15,890
18,700
15,480
17,850
15,170
17,200
14,790
720
19,350
15,410
18,430
15,010
17,600
14,710
16,950
14,340
1.75
1.84
880
15,300
12,560
14,570
12,230
13,910
11,980
13,410
11,690
800
15,060
12,200
14,350
11,880
13,700
11,640
13,200
11,350
720
14,840
11,830
14,140
11,520
13,500
11,290
13,010
11,000
Notes:
(1) Performance based on water as the chilled fluid.
(2) Pressure drop is for the coil only and does not Include a valve�
(3) Unit shipped with coil stubbed through the cabinet and capped�
(4) Pressure drops over 10 Ft. H20 are considered excessive.
Contact the factory for a special coil selection to meet your specific parameters.