Installation, Operation and Maintenance Manual
Marvel Plus
16
Subject to change without notice.
120.5-IM (1018)
Day Min/Max Screen
U01
Current 24/HR
Period
Low High
Temp:
047°F 077°F
Hum:
040% 067°F
The day min/max screen shows the high and low return air
temperature and humidity for the current 24 hour period�
Alarm History Screen
Alarm History
D: 05/10/13
T: 12:07
HIGH SUPPLY TEMP
Supply Temp: 150
Return Temp: 77
The alarm history screens document the alarms that
occurred, supply and return air temperatures at the time the
alarm occurred and the time and date of alarm� Up to 50
alarms may be stored in the alarm history pages� Use the
or buttons to page through the alarm history pages�
Set Day, Time, Date and Daylight Savings
Screen
U01 Real Time Clock
Day: Saturday
Time: 12:16
Date: 05/10/2013
Daylight Savings:
Yes
Sets the appropriate day of the week, time, date and day-
light savings time� Set up of the real time clock is important
to be able to record alarm history or for following scheduled
occupied and unoccupied times�
Schedule
For the system to follow an occupancy schedule, a Start
and End period must be set for each day of the week� If
the control schedule is set to 00:00 for both start and end
schedules, the system will remain constantly occupied�
Up to 20 Holiday occupancy schedules may be programmed
into the system� For the holiday schedule, a start date is
programmed and end date is programmed�
Occupied Control
Enable Schedule >
Yes
This screen is used to enable or disable the occupancy
schedule�
U01 OCCUPIED
Monday
> 07:00
Tuesday
> 07:00
Wednesday > 07:00
Thursday
> 07:00
Friday
> 07:00
Saturday
> 00:00
Sunday
> 00:00
U01 UNOCCUPIED
Monday
> 17:00
Tuesday
> 17:00
Wednesday > 17:00
Thursday
> 17:00
Friday
> 17:00
Saturday
> 00:00
Sunday
> 00:00