035-20209-000-A-0904

4

Unitary Products Group

Disconnect wire 138/PR from terminal (T3) on 
contactor (M5).

Extend wire 136/BLK to terminal (96 / U) located 
on the VLT6000 control using wires in conduit 
#1.

Extend wire 137/BRN to terminal (97 / V).

Extend wire 138/PR to terminal (98 / W).

Connect (BLK) wire of power harness to terminal 
(T1) on contactor (M5) and to terminal (91 / L1) 
on the VLT6000 control using shielded cable in 
conduit #2.

Connect (RED) wire of power harness to termi-
nal (T2) on contactor (M5) and to terminal (92 / 
L2).

Connect (WHT) wire of power harness to termi-
nal (T3) on contactor (M5) and to terminal (93 / 
L3).

Connect bare wire of power harness to the 
grounding terminal on VLT6000 control.

13. The activation pressures are preset at the factory.

See Drive parameters below.

14. Remove existing low ambient switch (LAS) (See

Figure 8), located in the unit control box, and
replace with new 0

o

 low ambient switch (provided).

15. Install additional crankcase heaters on the com-

pressors of the system to which the VLT6000 con-
trol is to be applied. Wire each additional heater
parallel to the existing heater, utilizing the existing
ground.

16. Secure wiring in the unit control box in a neat work-

man like manner using wire ties.

17. Replace terminal access cover on VLT6000 con-

trol.

18. Replace lid on VLT6000 enclosure.

19. Close unit control box by replacing unit access

panel and restore power to the unit.

20. Verify proper unit operation.

 
A call for cooling closes the (M5) contactor power-
ing the VLT6000 control. As the discharge pres-
sure rises above 210 PSI. during startup, the
VLT6000 control will increase the speed of the con-
denser fan accordingly.

The unit’s scroll compressor produces a rapid rise 

in discharge pressure upon startup and this, 
depending on the ambient temperature, will result 
in full speed operation of the condenser fan.  After 
the discharge pressure has stabilized, the speed of 
the condenser fan may decrease especially during 
times when the ambient temperature is below 80

°

F.  

If the discharge pressure has stabilized and an 
additional compressor is energized, the speed of 
the condenser fan may increase, compensating for 
the rise in discharge pressure.

As the discharge pressure begins to fall below the 

210 PSI. setpoint, the drive will reduce the speed of 
the condenser fan.

As the ambient temperature drops below 40

°

F the 

condenser fan will slow to the minimum speed. The 
pressure controlled condenser fan will disengage 
when the discharge pressure drops below 180 
PSIG as the ambient temperature falls. The system 
discharge pressure will increase when the con-
denser fan is disengaged causing the VLT6000 
control to increase the condenser fan speed.

21. Contact your local branch or distributor for ques-

tions regarding installation.

NOTE: 

VLT6000

See Table 3 for the parameter settings in the 
drive. For specific instructions on the VLT6000, 
refer to the Danfoss manual shipped with the 
kit.

Содержание HA 300

Страница 1: ...ART NO DESCRIPTION 1 1 ea X denotes Model number needed for application 473 24615 00X VLT6000 Condenser Fan Speed Control and Enclosure 2 1 ea 025 38680 000 Pressure Transducer 3 1 ea 025 38681 000 Wire Harness Assembly 4 1 ea 025 37466 000 Power wire Harness 5 1 ea 023 20566 000 Tee Connector 6 2 ea 021 15529 000 Screw HEX 14 X 75 7 1 ea 025 10209 000 7 8 Bushing 8 2 ea 025 14284 000 1 3 8 Bushin...

Страница 2: ...e 3 Perform a leak test on fittings and connections before putting the system into operation NOTE This procedure must be repeated for each sys tem 5 Attach wiring harness assembly plug to transducer See Figure 4 Route sensor wires back to VLT6000 enclosure 6 Remove VLT6000 enclosure lid 7 Pass wires through the bushing provided using knock out located in the bottom of the VLT6000 enclosure 8 Acces...

Страница 3: ...conduit 1 insert three 14 Gage wires marked on both ends field supplied Conduit 2 should run from the bottom of the VLT6000 enclosure to the condensing unit con trol box using knock outs provided In conduit 2 insert shielded power cable sup plied in accessory Allow additional conduit length to remove the VLT Control enclosure from the top rail and place on side for servicing 12 Wire condenser fan ...

Страница 4: ...anel and restore power to the unit 20 Verify proper unit operation A call for cooling closes the M5 contactor power ing the VLT6000 control As the discharge pres sure rises above 210 PSI during startup the VLT6000 control will increase the speed of the con denser fan accordingly The unit s scroll compressor produces a rapid rise in discharge pressure upon startup and this depending on the ambient ...

Страница 5: ...0 FAN OVER LPS1 HPS1 LPS2 HPS2 HP1 LP1 BLU BLU 217 O 281 BL 216 O 214 BL P 9 S 9 SYS 1 System 1 215 BL 2 3 4 5 6 7 LAS1 284 BL 283 BL BLK BLK P 11 S 11 SYS 1 BOTTOM OF CONTROL BOARD RB1 LOW AMB FS1 FS2 1 1 1 2 3 4 5 6 7 8 9 10 FAN OVER LPS1 HPS1 LPS2 HPS2 HP2 LP2 GRA GRA 247 Y 279 GY 248 Y 249 GY P 9 S 9 SYS 2 System 2 250 GY 2 3 4 5 6 7 LAS2 286 BL 285 BL BLK BLK P 11 S 11 SYS 2 BOTTOM OF CONTROL...

Страница 6: ... T3 M GND 1 2 3 4 BLK BRN PRP GRN Pressure Transducer System 1 RED WHT BLK T1 L1 T2 L2 T3 L3 VLT 6000 CONTROL TERMINALS 154 BK 155 BR 156 PR M7 1 M7 3 M7 2 P 17 S 17 FM 3 T1 T2 T3 M GND 1 2 3 4 BLK BRN PRP GRN RED WHT BLK Pressure Transducer System 2 OUTPUT POWER MOTOR TB INPUT POWER MAINS TB OUTPUT POWER MOTOR TB 91 L1 92 L2 93 L3 U 96 V 97 W 98 50 53 54 55 50 53 54 55 91 L1 92 L2 93 L3 U 96 V 97...

Страница 7: ... 207 10 seconds Ramp down time 209 Frequency to operate upon loss of analog input signal 210 External preset Reference location external transducer 211 0 Preset reference 1 212 0 Preset reference 2 213 0 Preset reference 3 214 0 Preset reference 4 216 1 Frequency bypass bandwidth 217 41 Frequency bypass 1 skip 41 Hz motor speed 300 No operation Digital input 16 301 No operation Digital input 17 30...

Страница 8: ...mum speed before shutting off part of sleep mode 404 Set about 1 Hertz above 201 part of sleep mode 405 Frequecy to turn back on part of sleep mode 406 413 0 psi Pressure value at minimum transducer signal 414 500 psi Pressure value at maximum transducer signal 415 PSI 2 Text string to display on the keypad 417 MAX Feedback function 418 210 psi Desired pressure to maintain 420 Inverse Control resp...