035-20209-000-A-0904

2

Unitary Products Group

1.

Disconnect all electrical power to the unit.

2.

Remove the condensing unit control box access
panel.

3.

Install the VLT6000 enclosure with the provided
screws. Mounting holes are pre-punched in the top
rails to locate the enclosure near the condensing
unit control box. See Figure 7.

4.

Attach the pressure transducers to the connection
tee (provided in accessory). The pressure trans-
ducer has a ¼ In. SAE female flare with Schrader
valve depressor for mounting to the tee. 
See Figure 2.

Hand thread the transducer to the tee.

Tighten and secure the connection.

Remove the Schrader valve cap from the dis-
charge line port (provided).

Hand thread the tee to the discharge line port.

Tighten and secure the connection, making sure 
the transducer is mounted vertically. See Figure 
3.

Perform a leak test on fittings and connections 
before putting the system into operation.

NOTE: 

This procedure must be repeated for each sys-
tem.

5.

Attach wiring harness assembly plug to transducer.
See Figure 4. Route sensor wires back to VLT6000
enclosure.

6.

Remove VLT6000 enclosure lid.

7.

Pass wires through the bushing (provided), using
knock out located in the bottom of the VLT6000
enclosure.

8.

Access the VLT6000 control terminal blocks. See
Figure 6. 

9.

Remove the terminal access cover. See Figure 5.

Before installing accessory read all of this installation
instruction.

FIGURE 2 - PRESSURE TRANSDUCER

Do not remove the plastic plugs from the transducers
until they are ready to be installed.

INSERT WIRING

HARNESS PLUG

¼ In. SAE FEMALE FITTING

WITH SCHRADER VALVE DEPRESSOR

FIGURE 3 - PRESSURE TRANSDUCER MOUNTING

FIGURE 4 - WIRE HARNESS ASSEMBLY

MOUNT

TRANSDUCER

VERTICALLY

TEE

TO

 DISCHARGE

 LINE

PORT

MOUNT

TRANSDUCER

VERTICALLY

TO DISCHARGE

LINE PORT

RED WIRE = 10.0 VDC SUPPLY
BLACK WIRE = COMMON

WHITE WIRE = OUTPUT

Содержание HA 300

Страница 1: ...ART NO DESCRIPTION 1 1 ea X denotes Model number needed for application 473 24615 00X VLT6000 Condenser Fan Speed Control and Enclosure 2 1 ea 025 38680 000 Pressure Transducer 3 1 ea 025 38681 000 Wire Harness Assembly 4 1 ea 025 37466 000 Power wire Harness 5 1 ea 023 20566 000 Tee Connector 6 2 ea 021 15529 000 Screw HEX 14 X 75 7 1 ea 025 10209 000 7 8 Bushing 8 2 ea 025 14284 000 1 3 8 Bushin...

Страница 2: ...e 3 Perform a leak test on fittings and connections before putting the system into operation NOTE This procedure must be repeated for each sys tem 5 Attach wiring harness assembly plug to transducer See Figure 4 Route sensor wires back to VLT6000 enclosure 6 Remove VLT6000 enclosure lid 7 Pass wires through the bushing provided using knock out located in the bottom of the VLT6000 enclosure 8 Acces...

Страница 3: ...conduit 1 insert three 14 Gage wires marked on both ends field supplied Conduit 2 should run from the bottom of the VLT6000 enclosure to the condensing unit con trol box using knock outs provided In conduit 2 insert shielded power cable sup plied in accessory Allow additional conduit length to remove the VLT Control enclosure from the top rail and place on side for servicing 12 Wire condenser fan ...

Страница 4: ...anel and restore power to the unit 20 Verify proper unit operation A call for cooling closes the M5 contactor power ing the VLT6000 control As the discharge pres sure rises above 210 PSI during startup the VLT6000 control will increase the speed of the con denser fan accordingly The unit s scroll compressor produces a rapid rise in discharge pressure upon startup and this depending on the ambient ...

Страница 5: ...0 FAN OVER LPS1 HPS1 LPS2 HPS2 HP1 LP1 BLU BLU 217 O 281 BL 216 O 214 BL P 9 S 9 SYS 1 System 1 215 BL 2 3 4 5 6 7 LAS1 284 BL 283 BL BLK BLK P 11 S 11 SYS 1 BOTTOM OF CONTROL BOARD RB1 LOW AMB FS1 FS2 1 1 1 2 3 4 5 6 7 8 9 10 FAN OVER LPS1 HPS1 LPS2 HPS2 HP2 LP2 GRA GRA 247 Y 279 GY 248 Y 249 GY P 9 S 9 SYS 2 System 2 250 GY 2 3 4 5 6 7 LAS2 286 BL 285 BL BLK BLK P 11 S 11 SYS 2 BOTTOM OF CONTROL...

Страница 6: ... T3 M GND 1 2 3 4 BLK BRN PRP GRN Pressure Transducer System 1 RED WHT BLK T1 L1 T2 L2 T3 L3 VLT 6000 CONTROL TERMINALS 154 BK 155 BR 156 PR M7 1 M7 3 M7 2 P 17 S 17 FM 3 T1 T2 T3 M GND 1 2 3 4 BLK BRN PRP GRN RED WHT BLK Pressure Transducer System 2 OUTPUT POWER MOTOR TB INPUT POWER MAINS TB OUTPUT POWER MOTOR TB 91 L1 92 L2 93 L3 U 96 V 97 W 98 50 53 54 55 50 53 54 55 91 L1 92 L2 93 L3 U 96 V 97...

Страница 7: ... 207 10 seconds Ramp down time 209 Frequency to operate upon loss of analog input signal 210 External preset Reference location external transducer 211 0 Preset reference 1 212 0 Preset reference 2 213 0 Preset reference 3 214 0 Preset reference 4 216 1 Frequency bypass bandwidth 217 41 Frequency bypass 1 skip 41 Hz motor speed 300 No operation Digital input 16 301 No operation Digital input 17 30...

Страница 8: ...mum speed before shutting off part of sleep mode 404 Set about 1 Hertz above 201 part of sleep mode 405 Frequecy to turn back on part of sleep mode 406 413 0 psi Pressure value at minimum transducer signal 414 500 psi Pressure value at maximum transducer signal 415 PSI 2 Text string to display on the keypad 417 MAX Feedback function 418 210 psi Desired pressure to maintain 420 Inverse Control resp...