background image

035-20209-000-A-0904

Unitary Products Group

3

10. Wire transducers to the VLT6000 control. 

See Figure 6.

Route power wires, motor leads, and transducer 
signal wires through separate knockouts. See 
Figure 6.

Connect White Wire from Transducer to Terminal 
(53) on the VLT6000.

Connect Black Wire from Transducer to Terminal 
(55). 

Connect Red Wire from Transducer to Terminal 
(50).

Connect Bare (shield) Wire from Transducer to 
Grounding Terminal.

NOTE: 

All Wiring must comply with prevailing Local
and National wiring codes and ordinances.

11. Cut two lengths of flexible conduit (Field Supplied)

to connect from the VLT6000 Control to the con-
densing unit control box.

Conduit #1 should run from the bottom of the 
VLT6000 enclosure to the condensing unit con-
trol box, using knock outs provided.

In conduit #1 insert three # 14 Gage wires 
marked on both ends (field supplied).

Conduit #2 should run from the bottom of the 
VLT6000 enclosure to the condensing unit con-
trol box, using knock outs provided.

In conduit #2 insert shielded power cable sup-
plied in accessory.

Allow additional conduit length to remove the 
VLT Control enclosure from the top rail and place 
on side for servicing. 

12. Wire condenser fan motor #1 to the VLT6000 con-

trol. See Figure 6, and the SWD in Figure 9. The
VLT6000 must be wired to operate fan motor #1.
Factory installed pressure switches control fan
motor #2.

Disconnect wire 136/BLK from terminal (T1) on 
contactor (M5).

Disconnect wire 137/BRN from terminal (T2) on 
contactor (M5).

FIGURE 5 - VFD66 CONTROL TERMINAL BLOCKS

FIGURE 6 - P399 PRESSURE TRANSDUCER 

WIRING

CONTROL

TERMINAL

BLOCK

INPUT

POWER

(MAINS)

TERMINAL

BLOCK

OUTPUT

POWER

(MOTOR)

TERMINAL

BLOCK

FIGURE 7 - FAN MOTOR #1 LOCATION

FAN MOTOR # 1

FAN MOTOR # 2

FAN MOTOR # 3

FAN MOTOR # 4

VLT6000 ENCLOSURE

VLT6000 ENCLOSURE

Содержание HA 300

Страница 1: ...ART NO DESCRIPTION 1 1 ea X denotes Model number needed for application 473 24615 00X VLT6000 Condenser Fan Speed Control and Enclosure 2 1 ea 025 38680 000 Pressure Transducer 3 1 ea 025 38681 000 Wire Harness Assembly 4 1 ea 025 37466 000 Power wire Harness 5 1 ea 023 20566 000 Tee Connector 6 2 ea 021 15529 000 Screw HEX 14 X 75 7 1 ea 025 10209 000 7 8 Bushing 8 2 ea 025 14284 000 1 3 8 Bushin...

Страница 2: ...e 3 Perform a leak test on fittings and connections before putting the system into operation NOTE This procedure must be repeated for each sys tem 5 Attach wiring harness assembly plug to transducer See Figure 4 Route sensor wires back to VLT6000 enclosure 6 Remove VLT6000 enclosure lid 7 Pass wires through the bushing provided using knock out located in the bottom of the VLT6000 enclosure 8 Acces...

Страница 3: ...conduit 1 insert three 14 Gage wires marked on both ends field supplied Conduit 2 should run from the bottom of the VLT6000 enclosure to the condensing unit con trol box using knock outs provided In conduit 2 insert shielded power cable sup plied in accessory Allow additional conduit length to remove the VLT Control enclosure from the top rail and place on side for servicing 12 Wire condenser fan ...

Страница 4: ...anel and restore power to the unit 20 Verify proper unit operation A call for cooling closes the M5 contactor power ing the VLT6000 control As the discharge pres sure rises above 210 PSI during startup the VLT6000 control will increase the speed of the con denser fan accordingly The unit s scroll compressor produces a rapid rise in discharge pressure upon startup and this depending on the ambient ...

Страница 5: ...0 FAN OVER LPS1 HPS1 LPS2 HPS2 HP1 LP1 BLU BLU 217 O 281 BL 216 O 214 BL P 9 S 9 SYS 1 System 1 215 BL 2 3 4 5 6 7 LAS1 284 BL 283 BL BLK BLK P 11 S 11 SYS 1 BOTTOM OF CONTROL BOARD RB1 LOW AMB FS1 FS2 1 1 1 2 3 4 5 6 7 8 9 10 FAN OVER LPS1 HPS1 LPS2 HPS2 HP2 LP2 GRA GRA 247 Y 279 GY 248 Y 249 GY P 9 S 9 SYS 2 System 2 250 GY 2 3 4 5 6 7 LAS2 286 BL 285 BL BLK BLK P 11 S 11 SYS 2 BOTTOM OF CONTROL...

Страница 6: ... T3 M GND 1 2 3 4 BLK BRN PRP GRN Pressure Transducer System 1 RED WHT BLK T1 L1 T2 L2 T3 L3 VLT 6000 CONTROL TERMINALS 154 BK 155 BR 156 PR M7 1 M7 3 M7 2 P 17 S 17 FM 3 T1 T2 T3 M GND 1 2 3 4 BLK BRN PRP GRN RED WHT BLK Pressure Transducer System 2 OUTPUT POWER MOTOR TB INPUT POWER MAINS TB OUTPUT POWER MOTOR TB 91 L1 92 L2 93 L3 U 96 V 97 W 98 50 53 54 55 50 53 54 55 91 L1 92 L2 93 L3 U 96 V 97...

Страница 7: ... 207 10 seconds Ramp down time 209 Frequency to operate upon loss of analog input signal 210 External preset Reference location external transducer 211 0 Preset reference 1 212 0 Preset reference 2 213 0 Preset reference 3 214 0 Preset reference 4 216 1 Frequency bypass bandwidth 217 41 Frequency bypass 1 skip 41 Hz motor speed 300 No operation Digital input 16 301 No operation Digital input 17 30...

Страница 8: ...mum speed before shutting off part of sleep mode 404 Set about 1 Hertz above 201 part of sleep mode 405 Frequecy to turn back on part of sleep mode 406 413 0 psi Pressure value at minimum transducer signal 414 500 psi Pressure value at maximum transducer signal 415 PSI 2 Text string to display on the keypad 417 MAX Feedback function 418 210 psi Desired pressure to maintain 420 Inverse Control resp...

Отзывы: