ACCESSORY KIT INSTALLATION INSTRUCTIONS

Low Ambient Accessory

For Air Cooled Split-System Air Conditioners

HA 300, HB 360 / 480 / 600, HF-25, HL-30 / -40 / -50 Models

035-20209-000-A-0904

GENERAL

These split-system condensing units are designed to
operate at ambient temperatures down to 40°F. This
accessory will insure safe operation at ambient temper-
atures down to 0°F. The VLT6000 control monitors the
refrigerant system and will vary the condenser fan
speed based on the discharge pressure. One controller
is required for each fan to be controlled. Therefore, two
accessory kits are required for each unit. This instruc-
tion provides all the necessary information to properly
field-install a low ambient accessory on the condensing
units listed in Table 1. Components that are supplied in
the respective accessory are listed in Table 2, and pic-
tured in Figure 1. 

 

TABLE 1: APPLICATION DATA

ACCESSORY MODEL #

VOLTAGE

UNIT

2LA04702658

575

HA 300, HF -25

2LA04702858

575

HB 360, HL -30 

2LA04702958

575

HB 480, HL -40

2LA04703058

575

HB 600, HL -50

TABLE 2: ACCESSORY COMPONENTS

ITEM

QTY.

PART NO.

DESCRIPTION

1*

1

*

 ea

*.

“X” denotes Model number needed for application.

473-24615-00X*

VLT6000 Condenser Fan Speed

 Control and Enclosure

2

1 ea

025-38680-000

Pressure Transducer

3

1 ea

025-38681-000

Wire Harness Assembly

4

1 ea

025-37466-000

Power wire Harness

5

1 ea

023-20566-000

Tee Connector

6

2 ea

021-15529-000

Screw HEX ¼-14 X.75

7

1 ea

025-10209-000

7/8 Bushing

8

2 ea

025-14284-000

1 3/8 Bushing

9

6 ea

025-09607-000

Wire Tie

10

1 ea

025-37455-000

0º Degree Switch

11

†. Crankcase Heaters supplied are dependent on accessory 

ordered.

2 ea

025-37425-575

30/40 Ton Crankcase Heater

2 ea

025-37474-575

25/50 Ton Crankcase Heater

FIGURE 1 - ACCESSORY COMPONENTS

The 2LA047 series low ambient accessories are
intended for use with the 25-50 Ton Split System con-
densing units only. UPG cannot guarantee proper
operation for any application of this VLT6000 control-
ler for other equipment or applications. Contact your
local branch or distributor for any application related
questions.

Improper installation, adjustment, service or mainte-
nance can cause injury or property damage. There-
fore, only a qualified installer or qualified service
personnel should perform this conversion.

If the unit is connected to power sources, make sure
that all electrical power to the unit has been discon-
nected.

Содержание HA 300

Страница 1: ...ART NO DESCRIPTION 1 1 ea X denotes Model number needed for application 473 24615 00X VLT6000 Condenser Fan Speed Control and Enclosure 2 1 ea 025 38680 000 Pressure Transducer 3 1 ea 025 38681 000 Wire Harness Assembly 4 1 ea 025 37466 000 Power wire Harness 5 1 ea 023 20566 000 Tee Connector 6 2 ea 021 15529 000 Screw HEX 14 X 75 7 1 ea 025 10209 000 7 8 Bushing 8 2 ea 025 14284 000 1 3 8 Bushin...

Страница 2: ...e 3 Perform a leak test on fittings and connections before putting the system into operation NOTE This procedure must be repeated for each sys tem 5 Attach wiring harness assembly plug to transducer See Figure 4 Route sensor wires back to VLT6000 enclosure 6 Remove VLT6000 enclosure lid 7 Pass wires through the bushing provided using knock out located in the bottom of the VLT6000 enclosure 8 Acces...

Страница 3: ...conduit 1 insert three 14 Gage wires marked on both ends field supplied Conduit 2 should run from the bottom of the VLT6000 enclosure to the condensing unit con trol box using knock outs provided In conduit 2 insert shielded power cable sup plied in accessory Allow additional conduit length to remove the VLT Control enclosure from the top rail and place on side for servicing 12 Wire condenser fan ...

Страница 4: ...anel and restore power to the unit 20 Verify proper unit operation A call for cooling closes the M5 contactor power ing the VLT6000 control As the discharge pres sure rises above 210 PSI during startup the VLT6000 control will increase the speed of the con denser fan accordingly The unit s scroll compressor produces a rapid rise in discharge pressure upon startup and this depending on the ambient ...

Страница 5: ...0 FAN OVER LPS1 HPS1 LPS2 HPS2 HP1 LP1 BLU BLU 217 O 281 BL 216 O 214 BL P 9 S 9 SYS 1 System 1 215 BL 2 3 4 5 6 7 LAS1 284 BL 283 BL BLK BLK P 11 S 11 SYS 1 BOTTOM OF CONTROL BOARD RB1 LOW AMB FS1 FS2 1 1 1 2 3 4 5 6 7 8 9 10 FAN OVER LPS1 HPS1 LPS2 HPS2 HP2 LP2 GRA GRA 247 Y 279 GY 248 Y 249 GY P 9 S 9 SYS 2 System 2 250 GY 2 3 4 5 6 7 LAS2 286 BL 285 BL BLK BLK P 11 S 11 SYS 2 BOTTOM OF CONTROL...

Страница 6: ... T3 M GND 1 2 3 4 BLK BRN PRP GRN Pressure Transducer System 1 RED WHT BLK T1 L1 T2 L2 T3 L3 VLT 6000 CONTROL TERMINALS 154 BK 155 BR 156 PR M7 1 M7 3 M7 2 P 17 S 17 FM 3 T1 T2 T3 M GND 1 2 3 4 BLK BRN PRP GRN RED WHT BLK Pressure Transducer System 2 OUTPUT POWER MOTOR TB INPUT POWER MAINS TB OUTPUT POWER MOTOR TB 91 L1 92 L2 93 L3 U 96 V 97 W 98 50 53 54 55 50 53 54 55 91 L1 92 L2 93 L3 U 96 V 97...

Страница 7: ... 207 10 seconds Ramp down time 209 Frequency to operate upon loss of analog input signal 210 External preset Reference location external transducer 211 0 Preset reference 1 212 0 Preset reference 2 213 0 Preset reference 3 214 0 Preset reference 4 216 1 Frequency bypass bandwidth 217 41 Frequency bypass 1 skip 41 Hz motor speed 300 No operation Digital input 16 301 No operation Digital input 17 30...

Страница 8: ...mum speed before shutting off part of sleep mode 404 Set about 1 Hertz above 201 part of sleep mode 405 Frequecy to turn back on part of sleep mode 406 413 0 psi Pressure value at minimum transducer signal 414 500 psi Pressure value at maximum transducer signal 415 PSI 2 Text string to display on the keypad 417 MAX Feedback function 418 210 psi Desired pressure to maintain 420 Inverse Control resp...