5.Status LED
3
5.
Status LED
LED expresses the status of communication.
6.
PLC Address
F372A/F377A enables to change the numbers of occupied stations by its setting.
Be careful the assignment of station number, double used station number is not available for PLC.
The address of remote (F372A/F377A) will be changed in accordance with the assignment of
station number.
Therefore, the address data of the F372A/F377A also changes according to Station No.
The following address map is in the state of Station No.1.
Name of LED
Light ON
Light OFF
Blinks
RUN
- Normal
- Reset Action
- No Communication
-----
SD
- Transmitting
-----
-----
RD
- Receiving
-----
-----
ERR
- Setting Error
- CRC Error
- Fault
- Normal
-----
Station
No.
Remote Input
Remote Output
Remote Resister
M
→
R
R
→
M
1
RX0000
RY0000
RWw0000
RWr0000
00E0H
0160H
01E0H
02E0H
2
RX0020
RY0020
RWw0004
RWr0004
00E2H
0162H
01E4H
02E4H
3
RX0040
RY0040
RWw0008
RWr0008
00E4H
0164H
01E8H
02E8H
When the F372A/F377A is a unit at both ends, terminator resistance must be
installed. (Confirm with the CC-Link specifications.) At this time, when the DA and
DB signal lines and resistance are to be connected to the connector, be aware
that poor contact may result if the nipping conditions differ between the leg of the
resistance and signal lines. There is a possibility of abnormal operation.
Attention