Secure the wires to the PC Board’s strain relief components using wire-ties. See Figure 2.
Note:
The default ring lug size is 5/16”. Other battery post adaptor sizes are available; contact factory for more
information.
Figure 11. Battery monitor PCB.
5.2.
BATTERY CELL LEAD CONNECTION TO THE SBM
The battery cell sensing leads are terminated with the 13 position female terminal blocks. This plugs onto the
connectors on the SBM board. How the cell voltage sense leads connect to the SBM board depends on the battery
configuration. The following figures show the connection between the battery and the SBM board for different
configurations of the battery. If more than two batteries are used in a particular configuration, simply repeat the
connection method for batteries 3 and 4.
WARNING
: Sense leads, which are connected to the battery string, pose a short circuit hazard. Each connection
to the SBM should be made BEFORE connecting sense wire to the ring lug terminals at the battery post. Cut and
dress the supplied sense leads during installation. A wire label card is shipped with each SBM; use these labels to
label the wires at the terminal end as well as the SBM end.
When connecting the battery sense leads, the lead should be dressed to the battery terminal BUT NOT
CONNECTED TO THE TERMINAL YET. Next, the SBM end of the lead should be cut, stripped, and inserted
into the pluggable terminal block receptacle. Only after the terminal block end has been terminated should the
ring terminal be attached to the battery bolt.
The battery bolt should be re-torqued to manufacturer's recommended torque when re-installing bolt.
NO-OX-ID is recommended on the battery sense lead ring lugs to minimize corrosion.