SIEMENS OIL BURNERS AUTOMATIC CONTROLLER LMO24 - 
LMO44

The LMO... burner controls are des igned for the  start-up and supervision

of single- or 2-stage forced draught oil  burners in  intermittent operation.

Yellow-burning f lames  are supervise d with p hotoresistive detectors

QRB..., blue-burning flames with blue-flame detectors QRC...
In terms of ho

using dimensions , elect rical co nnections and flame

detectors, the LMO... are identical to the LOA... oil burner controls.

Preconditions for startup

z

Burner control is reset

z

All contacts in the line are closed

z

No undervoltage

z

Flame detector is darkened, no extraneous light

Undervoltage

z

Safety  shut-down  in the operating position takes place sho

uld the

mains voltage drop below about AC 165 V

z

Restart is initiated when the mains voltage exceeds about
AC 175 V

Time supervision oil pre-heater

If th e oil pre-heate r’s  release contac t does not close within 10 minutes,

the burner control will initiate lock-out.

Controlled intermittent operation

After no  more than  24 hours of cont inuous operation, the burner  control

will initiate an automatic safety shut-down followed by a restart.

Control sequence in the event of fault

If lock-out occurs, th e outpu ts  for  the  fuel va lves and the  ignition  will

immediately be deactivated (< 1 second).

Lock-out

In the  event of lock-out, the  LMO... remains locked (lock-out  cannot be

changed), and the red signal lamp will light up. This status is also maintai-

ned in the case of a mains failure.

Resetting the burner

Whenever lock-out occurs, the  burner control can  immediately be  reset.

To do this, keep control     the lock-out reset button depressed for about 1

second (< 3 seconds).

Ignition program with LMO24.113A2

If the flame is lost during «TSA», the burner will be reignited, but not later

than at the end of «TSAmax.». This means that several ignition attempts

can be made during TSA (refer to «Program sequence»).

Limitation of repetitions

If the flame is lost  during operation, a maximum of 3 repet itions can be

made. If the flame is lost for the 4th time during operation, the burner will

initiate lo ck-out. T he rep etition count  is re started each time controlled

switching on by «R-W-SB» takes place.

Operation

Lock-out reset button «EK...» is  the key operatin g  element for

resetting the  burn er control  and fo r activating  / deactivating t he

diagnostic functions.

The multicolour  «LED» is  the  key indicating element  for bo th

visual diagnosis and interface diagnosis.

Red

Yellow

Green

Key

Off

Yellow

Green

Red

Diagnosis of cause of fault

After lock-out, the red fault signal lamp remains steady on.
In that condition, the visual diagnosis of the cause of fault according to the

error code table can be activated by pressing the lock-out reset button for

more than 3 seconds.

Cause

Response

After a mains failure

Restart

After voltage has fallen below the 
undervoltage threshold

Restart

In the event of a premature, faulty 
flame signal during «t1»

Lock-out at the end of «t1»

In the event of a premature, faulty 
flame signal during «tw»

Prevention of start-up, lock-
out after no more than 40 
seconds

If the burner does not ignite during 
«TSA»

Lock-out at the end of TSA

In the event the flame is lost during 
operation

Max. 3 repetitions, followed 
by lock-out

Oil pre-heater’s release contact does 
not close within 10 min.

Lock-out

APPENDIX

Colour code table

Status

Colour code

Colour

Oil pre-heater heats, 
waiting time «tw» 

●●●●●●●●●●●

Yellow

Ignition phase, ignition 
controlled

●❍●❍●❍●❍●❍●

Yellow-off

Operation, flame o.k.

❏❏❏❏❏❏❏❏❏❏❏❏

Green

Operation, flame not o.k.

❏❍❏❍❏❍❏❍❏❍❏

Green-off

Undervoltage

●▲●▲●▲●▲●▲●

Yellow-red

Fault, alarm

▲▲▲▲▲▲▲▲▲▲▲

Red

Output of fault code (refer 
to Fault code table)

▲❍▲❍▲❍▲❍▲❍

Red-off

Extraneous light prior to 
burner start-up

❏▲❏▲❏▲❏▲❏▲❏

Green-red

Interface diagnosis

▲▲▲▲▲▲▲▲▲▲▲▲▲▲

Red flicker light

Error code table

Blink code

Possible cause

2 blinks **

No establishment of flame at the end of TSA

z

Faulty or soiled fuel valves

z

Faulty or soiled flame detector

z

Poor adjustment of burner, no fuel

z

Faulty ignition

3 blinks ***

Free

4 blinks ****

Extraneous light on burner startup

5 blinks *****

Free

6 blinks ******

Free

7 blinks *******

Too manny losses of fleme during operation 
(limitattion og the number of repetitions)

z

Faulty or soiled fuel valves

z

Faulty or soiled flame detector

z

Poor adjustment of burner

8 blinks ********

Time supervision oil pre-heater

9 blinks *********

Free

10 blinks **********

Wiring error or internal error, output contacts

E K

Содержание PG70

Страница 1: ...MANUAL OF INSTALLATION USE MAINTENANCE PG60 PG70 PG81 M039191CA Rel 0 1 09 2011 BURNERS BRUCIATORI BRULERS BRENNER QUEMADORES Progressive Fully modulating Light oil burners...

Страница 2: ...otor rotation 16 ADJUSTMENTS 17 Adjustments brief description 17 Adjustment procedure 17 Adjustment by the Berger STM30 actuator 18 Adjustment by the Siemens SQL33 servocontrol 21 Fully modulating bur...

Страница 3: ...ins electricity gas oil or other fuel z Observe caution with hot burner components These are usually near to the flame and the fuel pre heating system they become hot during the unit operation and wil...

Страница 4: ...f toxic or explosive mixtures DIRECTIVES AND STANDARDS Gas burners European directives Directive 90 396 CEE Gas Appliances Directive 2006 95 EC on low voltage Directive 2004 108 CEE on electromagnetic...

Страница 5: ...of the combustion head determines the burner output The air comburent and fuel light oil are for ced into the combustion chamber as to let the flame light up How to interpret the burner s Performance...

Страница 6: ...ient temperature at 15 C BURNERS PG60 PG70 PG81 Output min max kW 151 791 291 1047 264 1900 Light oil rate min max kg h 13 67 25 88 22 160 Fuel Light oil Viscosity 1 3 E 20 C Power supply 400V 3N 50Hz...

Страница 7: ...BL C CL D E F G K H P M N PG60 760 244 442 1004 1202 270 300 570 153 240 182 190 M10 269 PG70 725 310 460 1035 1185 355 420 775 198 300 228 233 M10 330 PG81 825 340 490 1165 1315 355 420 775 234 300...

Страница 8: ...ccording to the procedure described on paragraph Handling the burner 3 place the 4 stud bolts 5 on the hole of the boiler s door according to the burner s drilling plate described on paragraph Overall...

Страница 9: ...in plants where gravity or ring feed systems are provided install an automatic interception device see n 4 Fig 2 Gravity circuit Fig 3 Ring circuit Fig 4 Suction circuit Key 1 Manual valve 2 Light oil...

Страница 10: ...nd fuel passing through the pump Burners are factory set for double pipe systems They can be suited for single pipe system recommended in the case of gravity feed as decribed before To change from a 1...

Страница 11: ...for a considerable length of time for example when there is a long suction line to bleed To avoid damages inject some lubrication oil into the vacuum inlet z Care must be taken when installing the pum...

Страница 12: ...umpSuntec AJ6 Viscosity 2 8 75 cSt Oil temperature 60 C max Inlet maximum pressure 2 bar Inlet minimum pressure 0 45 bar to avoid gasing Rated speed 3600 rpm max Suntec J6 J7 Oil viscosity 2 8 200 cSt...

Страница 13: ...exible hoses on the pump being careful to avoid exchanging the inlet and return lines see the arrows marked on the pump that show the inlet and the return see prevoius paragraph Suntec TA Oil viscosit...

Страница 14: ...hamber The part of fuel that is not burnt goes back to the tank through the return circuit The fuel amount to be burnt is adjusted by means of the burner actuator according to the adjustments set see...

Страница 15: ...w rate BERGONZO nozzle is provided set the return pressure at 11bar supply at 20bar on the delivery to get a 220kg h flow rate If the return pressure needed is 5bar instead act on the V adjusting scre...

Страница 16: ...se 230 V supply it is necessary to modify the electrical connections inside the terminal box of the electric motor and replace the thermal cutout relay RESPECT THE BASIC SAFETY RULES MAKE SURE OF THE...

Страница 17: ...he chimney Adjustment procedure To change the burner setting during the testing in the plant follow the next procedure according to the actuator model provided mod Berger STM30 or mod Siemens SQL z PG...

Страница 18: ...afely the high flame stage 4 Turn the burner on by means of its main switch A if the burner locks LED B on in the control panel press the RESET button C on the control panel see next picture see chapt...

Страница 19: ...ig 15 Fig 16 and act on on the pu mp adjusting screw VR see Fig 14 as to get the nozzle pressure at 20bar Bergonzo nozzles see diagram on Fig 10 Fig 15 Light oil manifold PG60 Fig 16 Combustion head w...

Страница 20: ...hange the position of the air damper rods 12 The burner is factory set with the head in its MAX position maximum output PG60 To let the burner operate at a lower output turn clockwise the VRT screw an...

Страница 21: ...t the previous step go on this way as to reach the desired low flame point 18 The low flame position must never match the ignition position that is why cam III must be set 20 30 more than the ignition...

Страница 22: ...minal no 6 or by setting MAN on the RWF40 modulator or by setting 0 by means of the CMF switch only for fully modulating burners 8 set the actuator on the manual mode MAN by means of the MAN AUTO swit...

Страница 23: ...1 when the cam has reached the high flame position 12 To adjust the air flow rate in the high flame stage loose the RA nut and screw VRA as to get the desired air flow rate moving the rod TR towards t...

Страница 24: ...turn the adjusting cam SV and set again the actuator to the AUTO mode to lock the adjusting cam 16 act on the V screw that mathces the bearings referring to the adjusting cam position 17 to adjust the...

Страница 25: ...w 1 Keep pushed for 5 seconds the EXIT button on the modulator for further details see the burner modulator manual when the LED with the hand symbol lights up press the arrow button driving the actuat...

Страница 26: ...THE RESET PUSHBUTTON IF A SECOND SHUT DOWN TAKES PLACE CALL THE TECHNICAL SERVICE WITHOUT TRYING TO RESET FURTHER WARNING DURING NORMAL OPERATION THE PARTS OF THE BURNER NEAREST TO THE GENERATOR COUPL...

Страница 27: ...ling lamp for light oil solenoid valve opening E Thermal cutout intervention signalling lamp F High flame operation signalling lamp G Low flame operation signalling lamp H Ignition transformer operati...

Страница 28: ...heir ceramic insulators clean adjust and replace if necessary z remove and clean the oil nozzles IMPORTANT do not clean the nozzles using metallic or sharp utensils use only solvents or steam at the e...

Страница 29: ...of a vacuum cleaner to scrape off the scale use a metallic brush Note to replace the combustion head reverse the procedure described above Removing the oil gun PG70 PG81 Once the combustion head is r...

Страница 30: ...4 Cleaning and replacing the detection photoresistor To clean replace the photoresistor proceed as follows 1 disconnect the system from the electrical power supply 2 shut off the fuel supply 3 remove...

Страница 31: ...rrent intensity with flame 45 A Maximum current intensity without flame 5 5 A Maximum possible current intensit with flamey 45 A 100 A 100 A THE BURNER DOESN T START THE BURNER REPEATS PRE PURGE NOISY...

Страница 32: ...PG60 G PR...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...PG60 G MD...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ......

Страница 41: ...PG70 PG81 G PR...

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ...PG70 PG81 G MD...

Страница 46: ......

Страница 47: ......

Страница 48: ......

Страница 49: ......

Страница 50: ...2340003 2 FLEXIBLE HOSES L 275 2340091 2340091 1 FLEXIBLE HOSES L 335 3 8 2340087 2340087 1 ADJUSTING CAM FOIL 2440013 2440013 2440013 2 SERVOCONTROL mod SIEMENS 2480009 2480022 2480022 1 SERVOCONTROL...

Страница 51: ...operation the burner will initiate lo ck out T he rep etition count is re started each time controlled switching on by R W SB takes place Operation Lock out reset button EK is the key operatin g elem...

Страница 52: ...e switch Z Ignition transformer t4 Interval from flame signal to release BV2 TSA Ignition safety time tw Waiting time for oil pre heating B Time of flame establishment C Operating position D Controlle...

Страница 53: ......

Страница 54: ......

Страница 55: ......

Страница 56: ......

Отзывы: