6
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Type
LO140
Model
G-. AB. S. *. A.
(1) (2) (3) (4) (5) (6)
(1) BURNER TYPE
LO140 – LO200
(2) FUEL
G – Light oil
(3) OPERATION
TN – Single-stage
AB – Double-stage
(4) BLAST TUBE
S - Standard
(5) DESTINATION COUNTRY
* - see burner ID plate
(6) VERSION
A – Standard
Y - Special
Specifications
BURNERS
LO140 G-.TN.. LO140 G-.AB.. LO200 G-.TN.. LO200 G-.AB..
Output
min. -max. kW
80 - 160
38 - 160
80 - 200
38 - 200
Fuel
Light oil
Oil flow rate
min. -max. kg/h
7 - 14
3 - 14
7 - 17
3 - 17
Viscosity
cSt @ 40 °C
2 – 7.4
Pressure at the oil train inlet
bar
1
Power supply
230V - 50Hz
Motor kW 0.18
Total power consumption
kW
0.48
Protection
IP40
Regulation
Single-stage Double-stage Single-stage Double-stage
Approx. weight
kg
18 18 19 19
Operating temperature
°C
-10 ÷ +50
Storage temperature
°C
-20 ÷ +60
Working service*
Intermittent
Light oil net calorific value Hi = 10210 kcal/kg
*.
NOTE ON THE BURNER WORKING SERVICE:
:
Burners provided with Siemens LOA24 control box:
for safety reasons, one controlled shutdown must take place every 24
hours.
Burners provided with Siemens LMO24-44 control box:
the control box automatically stops after 24h of continuous
working. The control box immediately starts up, automatically.
Biodiesel
:
Viscosity = 1.9 - 6 cSt @ 40 °C
Net calorific value Hi = 8950 kcal/kg